+86-312-6775656

HZJB-I 3 Phase Relay Protection Test Device

Oct 26, 2023

HZJB-I 3 Phase Relay Protection Test Device


Instruction to Front panel of Device Relay Protection HZJB-I

 

1 UA, UB, UC, UN, UX voltage output terminals for, including UX is a multifunctional voltage items, can set to four 3 U0 or the same period, or any voltage by a voltage value of output.

2 IA, IB, IC, IN for current output terminals, the current terminals (IA, IB, IC) on the right side of the small lights instructions which current output waveform distortion or whether there is open load

3 Switch input terminals, idle contact and 0-250 V potential compatible input, all 8road, is for the public end

4 LCD display

5 Rotate the mouse controller, should set all of the test data and process control all by its completion

6 "▲", "▼" button, test status, each as a, each according to its variables set by the step length add, subtract 1 step quantity; In the setting of data, each as a revised, the number of add, subtract 10

7 Power switch.

8 Connection PC communications mouth

9 Independent DC Output

10 Air outlet

11 The switch quantity empty contact output, no. 4. Idle contact capacity: DC: 220 V / 0.2 A; AC: 220 V / 0.5 A

13 Power supply Socket

14 Fuse for Voltage Output

¿ Instruction to Rear Panel of Device Relay Protection XZTJB-I

Device in the chassis backplane jacket has all the way adjustable dc power output, points 110 V and 220 V two gears, can be used as auxiliary power field test. The power supply is also equipped with a potentiometer, can be in the 80% to 110% range regulation. The power output current biggest 1.5 A. On another floor installed a cooling fans, and the power cord, grounding terminals and three insurance. Three insurance is A total power insurance (10 A / 250 V), two is voltage circuit insurance (2 A / 250 V), etc.

 

Specification

AC current output

Phase current output (effective value) 0~40A, Output Precision 0.2 degree

3 phase parallel current output (effective value) 0~120A

A Long-time Phase current 10A

Maximum output power of Phase current 450VA

Maximum output power of 3 parallel current 900VA

Maximum Permitted work time of 3 parallel current 10S

Frequency range ( fundamental) 20~1000Hz

Harmonic time 2~20

DC current output

Current output 0~±10A / phase, 0~±30A / 3 parallel

Output Precision 0.5 degree

AC voltage output

Phase voltage output (effective value) 0~120V Output Precision 0.2 degree

Line voltage output (effective value) 0~240V

Phase voltage / Line phase output power 80VA / 100VA

Frequency range (fundamental) 20~1000Hz

Harmonic time 1~20

DC voltage output

Phase voltage output range 0~±160V Output Precision 0.5 degree

Line voltage output range 0~±320V

Phase voltage / Line phase output power 70VA / 140VA

10 path digital input and 8 path digital output

Time measuring range 0.1ms ~ 9999s ,accuracy of measurement <0.1ms