HZ2181X 10A 3 Phase Transformer DC Winding Resistance Tester
HZ2181X 10A 3 Phase transformer DC resistance test instrument is a new instrument which designed for quick test of high-capacity transformer DC resistance with magnetic assist method.The method can test DC resistance of core five-limb and delta connected in the low voltage side of transformer quickly and accurately.It can be completed one time for normal YNd connected transformer,and there are different test methods for different type windings which improves greatly test speed.The instrument completes the whole process by MCU,which has perfect functions of protecing back-EMF and anti-interference on the scene, also has functions of storeing data with U-Disk, printing and communicateing with computer,protecting to avoid wrong connection AC380V. The instrument is a successor in level of 220kv-500kv transformer dc resistance test.

Main Technique Indexes and Using Conditions
Main technique indexes
Constant electric current: 1A 10A
Testing range: 1A: 100mΩ~20Ω
10A: 1mΩ~2Ω
1A Three channels:≤10Ω
10 A Three channels: ≤1Ω
Accuracy:±0.2%
Resolution ratio: 0.1μΩ
External dimension:418mm×290mm×300mm
Weight: 15kg
Using conditions
Environment temperature : 0ºC~40ºC
Environment humidity:≤80%RH
Power supply:AC198V~242V
Power frequency: (50±1)HZ
Measurement and Detection
A channel
Measuring current and range.
0.5A:1Ω~20Ω
5A:1mΩ ~2Ω
Test method.
0.5A select " sync 1A-YN" mode,5A select " sync 10A-YN" mode;Current terminals are IA,IB,volteage terminals are VA,VN.
B channel
Measuring current and range.
1A:100mΩ~20Ω
10A:1mΩ ~2Ω
Test method.
1A select " sync 1A-YN" mode,10A select " sync 10A-YN" mode;Current terminals are IA+IC(IA and IC are connected together to one terminal),volteage terminals are VN,VB.
C channel
Measuring current and range.
0.5A:1Ω~20Ω
5A:1mΩ ~2Ω
Test method.
0.5A select " sync 1A-YN" mode,5A select " sync 10A-YN" mode;Current terminals are IC,IB,volteage terminals are VC,VN.