+86-312-6775656

SFRA Test Report

Sep 17, 2021

(LV Mag-freq Curve)

 

1.Test Results

     Substation: q

       Location:

       Trans. #: a

     Trans. Mfr:

   Trans. Model:

    Date of Mfg:

     Serial No.:

    Rated Power:

  Rated Voltage:

         Phases: Single Phase

      Frequency: 50Hz

   Vector Group:

         Imp(%):

        Cooling: Oil Cooling

      Air Temp.: 25dC

            %RH:

      Oil Temp.: 25dC

       Tap Pos.:

Connection Pos.: Bushing

      Test Type: Routine Test

      Tested by:

        Company:

Standard: DL/T911-2016

QQ20210917102412 

Figure 1 Test Curves

#1:HV_OA_00,Air Temp.:25dC,Oil Temp.:25dC,Routine Test,2021-08-31 144420

#2:HV_OB_00,Air Temp.:25dC,Oil Temp.:25dC,Routine Test,2021-08-31 144539

#3:HV_OC_00,Air Temp.:25dC,Oil Temp.:25dC,Routine Test,2021-08-31 144704

#4:MV_OA_00,Air Temp.:25dC,Oil Temp.:25dC,Routine Test,2021-08-31 153545

#5:MV_OB_00,Air Temp.:25dC,Oil Temp.:25dC,Routine Test,2021-08-31 153814

#6:MV_OC_00,Air Temp.:25dC,Oil Temp.:25dC,Routine Test,2021-08-31 154027

#7:LV1_OA_00,Air Temp.:25dC,Oil Temp.:25dC,Routine Test,2021-08-31 154218

#8:LV1_OB_00,Air Temp.:25dC,Oil Temp.:25dC,Routine Test,2021-08-31 154418

#9:LV1_OC_00,Air Temp.:25dC,Oil Temp.:25dC,Routine Test,2021-08-31 154608

2.Data Analysis


R_lf

1-100kHz

R_mf

100-600kHz

R_hf

600-1000kHz

R_wf

10-1000kHz

Result

(Reference)

R1-2

5.01

5.28

4.11

5.36

Normal

R2-3

4.73

5.11

4.24

5.21

Normal

R1-3

4.79

5.14

4.04

5.26

Normal

R4-5

4.59

5.33

4.11

5.31

Normal

R5-6

4.31

5.26

4.43

5.29

Normal

R6-4

4.39

5.04

4.12

5.17

Normal

R7-8

4.52

5.29

4.17

5.32

Normal

R8-9

4.43

5.19

4.02

5.17

Normal

R9-7

4.78

5.13

4.35

5.25

Normal

 

3.Conclusion & Approval

Test conclusion:

 

 

Verifier:


Approver:


 


Send Inquiry