+86-312-6775656
HZ-2000F Transformer Tan Delta Dielectric Loss Test Machine

HZ-2000F Transformer Tan Delta Dielectric Loss Test Machine

HZ-2000F Transformer Tan Delta Dielectric Loss Test Machine The HZ-2000F dielectric loss tester adopts variable frequency power supply technology, utilizes microcontroller and modern electronic technology for automatic frequency conversion, analog-to-digital conversion, and data calculation;...
Product Details ofHZ-2000F Transformer Tan Delta Dielectric Loss Test Machine

Huazheng Electric Manufacturing (Baoding) Co., Ltd. is one of the leading manufacturers and suppliers of hz-2000f transformer tan delta dielectric loss test machine in China. Please feel free to buy high quality equipment for sale here from our factory. Good service and reasonable price are available.

 

HZ-2000F Transformer Tan Delta Dielectric Loss Test Machine

 

The HZ-2000F transformer tan delta dielectric loss tester adopts variable frequency power supply technology, utilizing a microcontroller and modern electronic technology for automatic frequency conversion, analog-to-digital conversion, and data calculation.

The power supply uses a high-power switching power supply, outputting pure sine waves at 45 Hz and 55 Hz with automatic voltage boosting up to a maximum of 10 kV. It automatically filters out 50 Hz interference, making it suitable for on-site testing in substations and other environments with high electromagnetic interference.

 

Feature

Digital Filtering: Fourier transform – high precision, auto measurement

Frequency Conversion: Eliminates 50Hz interference – reliable in strong EMI

Touchscreen: Full-touch large LCD – graphical interface, no training needed

Data Storage: Calendar chip + large memory – save, review, print anytime

Data Management: USB export – PC software for viewing/management

Easy Operation: Microprocessor-controlled – auto measurement

Integrated Design: Built-in standard capacitor + HV supply – reduces field wiring

High Accuracy: Meets oil dielectric loss requirements – add oil cup and test leads

Reverse Wiring Shielding: 220kV CVT bus grounded – 10kV reverse wiring on C11 (no wire removal)

AC Withstand: PT/CT secondary side and 400V low-voltage system withstand testing

 

Technical Indicators

Parameter Specification
Accuracy – Cx ±(reading × 1% + 1 pF)
Accuracy – tanδ ±(reading × 1% + 0.00040)
Anti‑interference Index Frequency‑conversion anti‑interference; maintains accuracy under 200% interference
Capacitance Range – Internal HV 3 pF ~ 60000 pF / 10 kV; 60 pF ~ 1.5 μF / 0.5 kV
Capacitance Range – External HV 3 pF ~ 1.5 μF / 10 kV; 60 pF ~ 30 μF / 0.5 kV
Resolution Up to 0.001 pF; 4 significant digits
tanδ Range No limit; resolution 0.001%
Test Current Range 10 μA ~ 5 A
Internal High Voltage – Setting Range 0.5 ~ 10 kV
Internal High Voltage – Resolution 1 V
Internal High Voltage – Accuracy ±(1.5% × reading + 10 V)
Internal High Voltage – Max Output Current 200 mA

 

lQDPKcrtGtmqmW_NAazNAyCw_iF2foFjEn0JNdw6T7ADAg_800_428

image012

image014

Request for quote_

Hot Tags: hz-2000f transformer tan delta dielectric loss test machine, China, suppliers, manufacturers, price, for sale, Automatic Transformer Tan Delta Test Kit, digital tan delta tester, tan delta test kit price, tan delta test equipment, transformer dielectric loss tester, dielectric loss tangent delta tester

Send Inquiry

(0/10)