+86-312-6775656
10kV Transformer Tan Delta Measuring Instrument

10kV Transformer Tan Delta Measuring Instrument

Huazheng HZ2581 10kV Transformer Tan Delta Measuring Instrument The HZ2581 Transformer Tan Delta Tester adopts variable-frequency power supply technology, integrating microcontrollers and electronic components to implement automatic frequency conversion, analog-to-digital conversion, and data processing. This...
Product Details of10kV Transformer Tan Delta Measuring Instrument

Huazheng Electric Manufacturing (Baoding) Co., Ltd. is one of the leading manufacturers and suppliers of 10kv transformer tan delta measuring instrument in China. Please feel free to buy high quality equipment for sale here from our factory. Good service and reasonable price are available.

 

10kV Transformer Tan Delta Measuring Instrument

 

The HZ2581 transformer tan delta tester adopts variable-frequency power supply technology, integrating microcontrollers and electronic components to implement automatic frequency conversion, analog-to-digital conversion, and data processing.

The variable-frequency power supply uses a high-power switching supply and outputs pure sine waves at a single frequency of 50Hz/60Hz and dual frequencies of 47.5Hz/52.5Hz, 45.0Hz/55.0Hz, 57.5Hz/62.5Hz, and 55.0Hz/65.0Hz. It supports automatic voltage regulation and can provide a voltage output of up to 10kV. With automatic 50Hz interference filtering, it is well suited for use in substations and other environments with strong electromagnetic interference.

 

Technical Indicators

1

service condition

-15℃∽40℃

RH<80%

2

anti-jamming principle

variable-frequency method

3

source

AC 220V±10%

generator with permit

4

high voltage output

0.5kV∽10kV

Every 0.1kV

accuracy

2%

Maximum current

200mA

capacity

2000VA

5

autogenerator

AC 0V∽50V/40A

single frequency 50.0Hz\60.0Hz adjustable

double frequency

45.0HZ/55.0HZ 47.5HZ/52.5HZ

55.0HZ/65.0HZ 57.5HZ/62.5HZ

6

resolution ratio

tgδ: 0.001%

Cx: 0.001pF

7

accuracy

△tgδ: ±(reading × 1.0% + 0.040%)

△Cx: ± (reading *1.0%+1.00PF)

8

measuring range

tgδ

unrestricted

Cx

15pF < Cx < 300nF

10kV

Cx≤60 nF

5kV

Cx≤150 nF

1kV

Cx≤300 nF

CVT test

Cx≤300 nF

9

External dimensions (main unit) (mm)

40cm*29cm*33cm

External dimensions (Attachment) (mm)

45cm*33cm*15cm

10

size of memory

200 groups support USB data storage

11

Weight (host)

25.5kg

Weight (Attachment Box)

5.18kg

 

Precautions

Comply with the requirements of the High Voltage Test Safety Work Regulations.

High-voltage testing requires at least two personnel: one operator and one supervisor.

The input voltage is AC 220 V ±10%, with a maximum of AC 264 V. Exceeding this limit may cause permanent damage, and the manufacturer will not provide warranty for such cases.

The instrument must be reliably grounded.

After testing, turn off the power switch. Do not disassemble or install high-voltage cables while powered on!

If the instrument malfunctions, turn off the power and wait approximately one minute before checking.

After completing the measurement, turn off the power switch and wait approximately one minute before disconnecting the wires.

The instrument should be protected from moisture and violent vibrations.

 

List

No.

Item

Qty

1

Test machine host

1

2

High voltage output cable

1

3

Sample input cable

1

4

CVT output cable

1

5

220V power cord

1

6

Earth wire

1

7

6.3A fuse

5

8

thermochromic paper

2

9

Work certificate

1

10

Operating instruction

1

11

Factory Inspection Report

1

 

lQDPKcrtGtmqmW_NAazNAyCw_iF2foFjEn0JNdw6T7ADAg_800_428

image006

image008

Request for quote_

Hot Tags: 10kv transformer tan delta measuring instrument, China, suppliers, manufacturers, price, for sale, tan delta test, tan delta test kit price, tan delta test set, capacitance and tan delta meter, capacitance and dissipation factor measuring bridge, transformer tan delta tester

Send Inquiry

(0/10)

clearall