HZCD80 SF6 Gas Breaker Purity Test System
Huazheng Electric Manufacturing (Baoding) Co., Ltd. is one of the leading manufacturers and suppliers of hzcd80 sf6 gas breaker purity test system in China. Please feel free to buy high quality equipment for sale here from our factory. Good service and reasonable price are available.
Product Overview
The HZCD80 SF6 Purity Analyzer is the latest intelligent measuring instrument developed by our company. This product uses a high brightness LCD touch screen as the human-machine interface. The English language interface is easy to operate and display all kinds of data in real time. High precision and fast response full touch screen is used as man-machine input, and multiple functions are switched freely. The instrument uses a large capacity and rechargeable battery, long standby time.
Tech Data
Measurement range: 0 ~ 100%(SF6 percentage)
Measurement accuracy: + 0.1 (90% ~ 100% range)
Discrimination rate: 0.01%.
Sampling flow: 0.5 ~ 0.8 l /min.
Response time: 15 s (response 90%).
Operation Steps
1. Warm up the machine for ten minutes. This process eliminates the effect of ambient temperature on the test results.
2. Connect SF6 device
1) Connect the thread end of the measuring pipe with the switch connector and tighten it with a wrench.
2) Then insert one end of the fast joint on the test pipe into the sampling port on the purity meter.
3) Connect the exhaust pipe to the vent.
3. Check the charge
When using DC power, please check the battery power displayed in the upper right corner. If the power is less than about 20%, please turn it off and continue to use it after charging.
4. Start measurement
First, all the needle valves on the pipe are measured, then the flow valve on the purity gauge panel is adjusted. The flow rate is adjusted to about 0.5L/M, and the gas purity of SF6 is measured.
5. Store data
After the equipment measurement is completed, the data can be saved in the instrument, and the operation menu can be adjusted according to the "HISTORY" key.
6. Measuring other equipment
After measuring a device, close the needle valve on the measuring line and the regulating valve on the purity meter. Remove the adapter from the SF6 electrical equipment. If you need to continue to measure other devices, follow the above steps to continue measuring the next device.
7. End of measurement
After the measurement is finished, turn off the purity instrument.
Matters need attention
1. The instrument should be placed in a safe position to prevent falls and avoid violent vibrations.
2. Do not measure corrosive gas.
3. When adjusting the gas flow, the flow valve should be slowly opened, so that the flow indicator within the range of 0.5 ~ 0.8 L/minute.
4. Before the instrument is used, it should be charged in time. When charging, simply insert the instrument's own power adapter into the charging port. Without turning on the instrument's power switch, the instrument will automatically charge. The charging time usually takes more than 5 hours.



Hot Tags: HZCD80 SF6 Gas Breaker Purity Test System, China, suppliers, manufacturers, price, for sale, HZCD-80, sf6 dew point analyzer, sf6 gas leak detector, sf6 gas density relay tester, sf6 dew point tester, sf6 gas density relay calibration system, sf6 test
Send Inquiry