HZSF-521 H2S SO2 Gas Detection SF6 Decomposition Products Tester

HZSF-521 H2S SO2 Gas Detection SF6 Decomposition Products Tester

HZSF-521 SF6 Decomposition Tester: Faults of SF6 electrical equipment are divided into body internal faults and operating mechanism faults.The internal faults involving solid insulation pose the greatest threat to the safety of equipment. The internal faults can be divided into discharge and overheating, and the discharge types...
Product Details ofHZSF-521 H2S SO2 Gas Detection SF6 Decomposition Products Tester

Huazheng Electric Manufacturing (Baoding) Co., Ltd. is one of the leading manufacturers and suppliers of hzsf-521 h2s so2 gas detection sf6 decomposition products tester in China. Please feel free to buy high quality equipment for sale here from our factory. Good service and reasonable price are available.

 

HZSF-521 SF6 Decomposition Products Tester

The HZSF-521 Series SF6 Decomposition Detector is an intelligent, high-sensitivity field instrument developed specifically for non-destructive, early-stage fault diagnostics in SF6SF6​ gas-insulated high-voltage apparatus (including Gas-Insulated Switchgear [GIS], SF6SF6​ circuit breakers, gas-insulated instrument transformers, and high-voltage bushings).

Diagnostic Purpose & Critical Problems Solved

Internal faults within SF6SF6​ electrical apparatus are categorized into mechanical operating mechanism defects and internal electrical/thermal degradation. Internal faults involving solid insulation (epoxy resin spacers, support insulators) represent the most severe threat to grid security, frequently initiating as low-energy partial discharges (floating potential discharge, ground discharge, or turn-to-turn insulation tracking) or localized overheating hotspots.

Because pure SF6SF6​ gas decomposes under high-energy discharge or severe thermal stress, it reacts with trace moisture and vaporized electrode metals to form characteristic corrosive by-products-predominantly Sulfur Dioxide (SO2SO2​) and Hydrogen Sulfide (H2SH2​S).

Traditional electrical insulation tests (such as power-frequency withstand or PD testing) require costly substation outages and often fail to detect latent micro-defects. The HZSF-521 provides live, non-invasive gas sampling by measuring trace SO2SO2​ and H2SH2​S concentrations down to 0.1 ppm. By analyzing by-product generation rates and gas ratios, substation engineers can pinpoint early-stage internal arcing, solid insulation erosion, and overheating hotspots before flashover insulation breakdown occurs.

Target Equipment Applications

Gas-Insulated Metal-Enclosed Switchgear (GIS / C-GIS from 10 kV to 1000 kV).

High-Voltage SF6​ Dead-Tank and Live-Tank Circuit Breakers (GCB).

SF6​ Gas-Insulated Power Transformers (GIT) and Instrument Transformers (CT / PT).

High-Voltage SF6​ Insulated Bushings and Gas-Insulated Busducts (GIB).

 

Technical Specifications

Parameter Specification Value Testing & Engineering Notes
Model HZSF-521 Series Intelligent dual-gas decomposition analyzer
Detected By-Product Gases SO2SO2​ (Sulfur Dioxide) and H2SH2​S (Hydrogen Sulfide) High-selectivity electrochemical sensor channels
Minimum Detection Limit 0.1 ppm Detects micro-discharge at inception stage
Measurement Range 0 ~ 100 ppm Standard range (customizable on request)
Measurement Accuracy ≤±0.1 ppm≤±0.1 ppm (when reading ≤2 ppm≤2 ppm)
≤±0.2 ppm≤±0.2 ppm (when reading >2 ppm>2 ppm)
Class-leading micro-concentration accuracy
Zero-Point Temperature Drift ≤±0.1 ppm≤±0.1 ppm Over operational temperature shift from +20 ℃+20 ℃ to +40 ℃+40 ℃
Repeatability ≤2%≤2% Evaluated for both SO2SO2​ and H2SH2​S channels
Measurement Cycle Time 2 ~ 3 minutes Real-time LCD update every 1 second after 2-min auto-zero
Sampling Gas Flow Rate Approximately 0.35 L/min Controlled via integrated needle flow valve
Operating Temperature -40 ℃ ~ +50 ℃ Extreme climate field readiness
Operating Humidity ≤ 95% RH (Non-condensing) Suitable for humid outdoor switchyards
Atmospheric Pressure Range 86 kPa ~ 106 kPa High-altitude and lowland standard rating
Internal Power Supply Built-in 4000 mAh rechargeable lithium battery Over 10 hours continuous operation on full charge
Chassis Dimensions 252 mm × 310 mm × 98 mm Ultra-compact ruggedized field casing
Net Instrument Weight 2.5 kg Extremely portable for elevated GIS ladder work
Communication Interface RS232 Serial Port Real-time terminal data streaming & micro-printer support

 

Compliance & Diagnostic Standards

Standard Reference Standard Title & Focus Area Application to HZSF-521 Decomposition Analysis
IEC 60480 Guidelines for the checking and treatment of sulfur hexafluoride (SF6SF6​) taken from electrical equipment and specification for its re-use Threshold criteria for reactive by-products (SO2+SOF2SO2​+SOF2​) and permissible contamination limits for in-service gas
IEC 62271-4 High-voltage switchgear and controlgear - Part 4: Handling procedures for sulphur hexafluoride (SF6SF6​) and its mixtures Safety procedures for gas sampling, decomposition by-product monitoring, and gas disposal
IEEE Std C37.122.1 IEEE Guide for Gas-Insulated Substations - Gas Quality & Diagnostics Diagnostic interpretation of chemical by-products generated by electric arcs and local spark discharges
DL/T 1205 Guidelines for fault diagnosis of SF6SF6​ electrical equipment by gas decomposition products Analytical criteria correlating SO2SO2​ and H2SH2​S ppm concentrations with internal discharge types and solid insulation involvement
DL/T 984 Guidelines for maintenance and management of SF6SF6​ electrical equipment In-service inspection periodicity and gas decomposition chemical alarm limits

 

Key Engineering Features

Simultaneous Dual-Gas Electrochemical Sensing: Integrates two dedicated, high-stability electrochemical sensors in a parallel gas manifold. Simultaneously samples and displays real-time SO2SO2​ and H2SH2​S concentrations without cross-channel interference.

Embedded Expert Fault Diagnosis Logic: Incorporates a microprocessor-driven fault diagnosis system that correlates measured SO2SO2​ and H2SH2​S ratios to classify internal fault categories:

High SO2SO2​ with negligible H2SH2​S: Spark discharge or localized metallic overheating.

Concurrent elevated SO2SO2​ and H2SH2​S: Severe discharge involving organic solid insulation (epoxy spacers/insulators).

Automated Startup Zero Self-Calibration: Upon power-up, the instrument initiates an automated 2-minute zero-point self-cleaning and calibration routine, ensuring sensor baseline stability before gas connection.

Micro-Flow Conservation Gas Circuit: Features an integrated precision needle regulating valve calibrated for low-consumption sampling at 0.35 L/min, minimizing SF6SF6​ gas loss from pressurized switchgear compartments during testing.

Alphanumeric Device ID Data Logging: Internal non-volatile memory stores measurement records with customizable 5-character alphanumeric equipment tags (supporting 0−90−9, A−ZA−Z, a−za−z), recording test time, date, and ppm values for longitudinal trending.

Flexible Calibration Routines: Supports both quick single-point KK-factor gain calibration and advanced 16-point linear multi-gas curve correction directly from the front panel menu.

Long-Endurance Field Battery System: Powered by a high-capacity 4000 mAh lithium battery pack delivering over 10 hours of cord-free testing, eliminating the need for AC extension cords in remote switchyards.

 

SF6 Decomposition Tester

FAQ

Why is monitoring SO₂ and H₂S decomposition by-products critical for GIS and SF₆ switchgear?

Pure SF₆ is chemically inert and non-toxic. When internal partial discharge, sparking, high-energy arcing, or severe thermal overheating above 200°C occurs, SF₆ decomposes into lower fluorides such as SF₄ and SF₂. In the presence of moisture and organic solid insulation, including epoxy spacers and support insulators, these fragments react to form stable, corrosive gaseous by-products, mainly sulfur dioxide (SO₂) and hydrogen sulfide (H₂S). Detecting these gases at sub-ppm levels lets maintenance teams find latent insulation degradation weeks or months before a flashover or gas-chamber failure.

How do engineers distinguish metallic overheating from solid-insulation discharge using decomposition gas data?

Per IEC 60480 and DL/T 1205, the gas pattern helps identify the source. When a discharge or surface tracking attacks epoxy resin insulation that contains organic sulfur and carbon compounds, both SO₂ and H₂S appear in significant concentrations. Metallic overheating of busbar contacts, or corona in clean gas without solid insulation, mainly raises SO₂, with virtually no H₂S. Normal high-energy switching also produces SO₂, but the level usually stabilizes unless the contacts are badly eroded.

Why is a low sampling flow rate of about 0.35 L/min important?

A flow of about 0.35 L/min lets the electrochemical sensor chamber reach dynamic equilibrium without excess pressure on the sensor membrane. Low-flow sampling also limits the amount of SF₆ drawn from sealed high-voltage compartments, so routine testing is less likely to trigger a low-pressure gas alarm.

What is the significance of the 2-minute startup self-calibration?

Electrochemical sensors can show a small baseline shift from residual gas in the manifold or from ambient temperature change. On power-up, the HZSF-521 runs an automatic 2-minute zero-point self-calibration and purges the internal pipeline before sample gas is admitted. This keeps the initial zero within ±0.1 ppm.

How should the gas circuit be purged between GIS compartments?

If a tested compartment contains a high concentration of SO₂ or H₂S, residual molecules can remain on the tubing walls. Before the next test, close the sampling valve, flush the manifold with ambient air or clean dry nitrogen, and confirm that the display returns below 0.1 ppm. If a high reading was found, a confirmation re-test after 5 minutes is recommended.

Can the HZSF-521 operate while connected to AC power?

Yes. The HZSF-521 has a built-in 4,000 mAh rechargeable lithium battery for more than 10 hours of continuous field use. In the laboratory or at a longer field station, it can be connected to AC 220 V through its dedicated charger, so the battery charges while measurement continues.

lQDPKcrtGtmqmW_NAazNAyCw_iF2foFjEn0JNdw6T7ADAg_800_428

Customer Visit

Case

Request for quote_

Hot Tags: HZSF-521 H2S SO2 Gas Detection SF6 Decomposition Products Tester, China, suppliers, manufacturers, price, for sale, SF6 Gas Tester, sf6 gas testing equipment, SF6 Decomposition Test Set, SF6 Decomposition Products Analyser, HZSF-821, sf6 test, sf6 decomposition analyzer, SF6 Gas Density Relay Calibrator, sf6 gas moisture analyzer, sf6 gas analyser, sf6 gas leak detector