1. Operation method
For the grounding resistance meter, trip the grounding wire and hit an auxiliary grounding pin. The ground electrode to be measured is to be separated from the grounding system, and the voltage electrode and current electrode must be driven into the soil at the specified distance as an auxiliary electrode for measurement. The operation is more complicated and laborious.
The clamp-on ground resistance tester is a non-contact measurement. You only need to clamp the jaw of the clamp meter to the ground wire to be tested, and the ground resistance value can be read from the clamp meter's LCD screen. The operation is very simple.
2. Measurement accuracy
The accuracy of the grounding resistance meter depends on the position between the auxiliary electrodes and the relative position between them and the grounding electrode. If the position of the auxiliary electrode is restricted and cannot meet the calculated value, it will cause the so-called distribution error. For the same ground electrode, different auxiliary electrode positions may cause the measurement results to have a degree of dispersion. And this dispersion will reduce the credibility of the measurement results.
The clamp ground resistance tester does not need auxiliary electrodes, and there is no error in the arrangement of electrodes. When the test is repeated, the consistency of the results is good.
3. Test environment
The grounding resistance meter adopts the voltage-current method, and two auxiliary grounding electrodes with relative position requirements must be inserted. Therefore, there must be soil that meets the position requirements near the test point.
The clamp ground resistance tester measures the loop resistance value, so the ground electrode to be tested must form a loop, and it cannot be directly measured for single-point grounding.
4. Other applications of clamp ground resistance tester
In many environments (such as computer rooms in basements or floors, lightning rods, elevators, gas stations, grounding bodies covered by concrete, and grounding bodies that cannot be separated from the system, etc.), use traditional grounding resistance meters to measure grounding resistance is very difficult. Although they are also single-point grounding, if there is a grounding body clamp meter available on site, their grounding resistance can be measured, and there is no need to disconnect the grounding electrode from the system during the test (see the instruction manual). The Fluke Clamp Ground Resistance Tester can measure ground faults that cannot be measured by traditional methods. For example, in a grounding system, the grounding resistance value of their grounding electrode is qualified, but the connection line between the grounding electrode and the lightning protection belt or the grounding overhead line may have too large contact resistance or even open circuit after long-term use, even though it is grounded. The grounding resistance of the pole is qualified, but the grounding system is unqualified.
5. For the same ground electrode, when the measurement results of the two instruments are quite different, please pay attention to the following issues:
(1) When testing with a traditional grounding resistance meter, whether the grounding down conductor is tripped (that is, whether the tested grounding electrode is separated from the grounding system). If it is not tripped, the resistance measured by the shaker is the parallel value of all grounding resistances of the grounding system. This parallel value is much smaller than the grounding resistance of the grounding electrode, and it is meaningless.
(2) my country's standard GL/T621-1997 "Grounding of AC Electrical Installations" stipulates: "The sum of the earth resistance of the earthing electrode or natural earthing electrode and the resistance of the earthing wire is called the earthing resistance of the earthing device." Generally speaking, it is traditional The ground resistance meter can only measure the ground resistance of the ground electrode, but cannot measure the resistance of the ground wire. The grounding resistance measured by the clamp meter is the sum of the grounding resistance of the grounding electrode and the resistance of the grounding wire, which fully meets the requirements of our country's standards.
(3) If the grounding system has only a few grounding electrodes, there will be some errors in the measurement with a clamp meter, which will generally be larger. If you want to get an accurate grounding resistance value, you can use the "Solution Program for Finite Point Grounding System" to solve it.