Test items |
Standard(μl/l, 20℃) |
|
Sulfur hexafluoride circuit breaker factory and overhaul (before the whole installation) should be measured respectively the breaking unit and pillar unit moisture value. |
≤150 |
|
The water value of the circuit breaker is measured by the inflatable interface at the lower part of the pillar. |
≤150 |
|
The water value of the circuit breaker is measured by the inflatable interface at the lower part of the pillar. The test period is specified in the "pre-test procedure". |
≤200 |
|
In operation, if necessary (air leakage in the breaking unit, disintegration of the over-breaking unit) sulfur hexafluoride circuit breaker should be measured separately by the self-sealing junction in the connecting box. |
≤300 |
SF6 circuit breaker moisture measurement requirements