SF6 circuit breaker moisture measurement requirements

Dec 12, 2023

Test items

Standard(μl/l, 20℃)

Sulfur hexafluoride circuit breaker factory and overhaul (before the whole installation) should be measured respectively the breaking unit and pillar unit moisture value.

≤150

The water value of the circuit breaker is measured by the inflatable interface at the lower part of the pillar.

≤150

The water value of the circuit breaker is measured by the inflatable interface at the lower part of the pillar. The test period is specified in the "pre-test procedure".

≤200

In operation, if necessary (air leakage in the breaking unit, disintegration of the over-breaking unit) sulfur hexafluoride circuit breaker should be measured separately by the self-sealing junction in the connecting box.

≤300