The voltage level selection of a DC resistance tester mainly depends on the size and nature of the measured resistance. For example, a 3-5A DC resistance tester is generally used for a 10kV voltage level; For voltage levels of 35kV, a 10A DC resistance tester is generally used; 20A DC resistance tester is usually used for 110kV voltage level; The 40A DC resistance tester is mainly used for voltage levels of 220kV. When selecting, it is important to note that the current should not be too high or too low, as excessive current may cause an increase in transformer temperature, leading to inaccurate resistance testing; If the current is too small, it may lead to an increase in the error of the test results.
In addition, the model selection of the DC resistance tester is also very important. For example, certain models of DC resistance testers may have a measurement range of 1 μ Ω to 20K Ω, with 7 optional ranges; Other models may have a measurement range of 1 μ Ω to 2M Ω, with 9 ranges available. Therefore, when selecting a DC resistance tester, users need to choose the appropriate model and measurement range based on actual needs and the size of the measured resistance.