1.Preparation Before Test
Connect the ground terminal (on the right side of the equipment) to the ground wire firmly before starting the equipment.
Sample the oil according to relevant standard. Adjust the electrode distance inside the oil cup with standard gauge. Clean the cup according to relevant requirements. Pour the sample into the cup and close the cap.
Switch on AC230V power supply after the above items are confirmed, ready for the test.
2.Testing
①Press the power switch and then enter the following interface:

② Setting of system parameters:
Press "Settings" key and enter the following interface:

Standard select
The user can choose the standard of test execution according to the need.
If you choose "Custom", you can choose boost conditions according to actual needs. The user-defined interface is as follows

Voltage of boosting stop: 10~80kV(adjustable)
Stand time: 0~15min(adjustable)
Interval of boosting: 0~5min(adjustable)
Stir Time: 0~120s(adjustable)/ CONT
Boosting frequency: 1~10times(adjustable)
Voltage boosting rate: 0.5 kV/s~5.0 kV/s(adjustable)
If other standards are selected, take the power standard DL/T 846.7-2016 as an example, as shown in the figure below,Stir time and Volt.rate are optional, click "
" to return to the previous page.

2) System set
(1)Autotype: ON/OFF,select by button.
(2)Time setting:When the instrument time is not accurate, can be adjusted
(3)Generally, users do not need to calibrate the instrument
(4)Device Information. You can view the device version, factory and other informatio,etc.
When setting is complete, click " " to save the settings and return to the main interface.
③ Test:
Press the "Test" key to enter the following interface:

After the static time is over, enter the boost interface automatically. Click "start" button to skip the static entry and enter the boost interface. Click " " to exit the test interface and return to the main interface.

If you click the "Stop" button, then stop the rise voltage
If you click the "Rise" button, then the voltage rises
If you click the "fall" button, then voltage drop
The first test ended, enter the delay interface

After the delay, the next test start until the boosting frequency is reached. Finally, the result is showed as follows:

Click"Sample No"to enter the sample number
④ Data Query
Press the "Query" key to enter the following interface:

Click the "PgUp" or "PgDn" button to flip pages to display test data at different test times.
Click the "Print" button to print test data displayed on the current interface.
Click on the "Del" button to delete the test data displayed in the current interface, but if you click on the blue icon in the upper right corner of the interface, you can delete all test data stored in the instrument. Please operate with caution.
By selecting the "USB" button, all test data stored by the instrument can be imported into the U disk. However, before clicking the button, make sure that the instrument is inserted into the U disk.