HZZGF 80kV 5mA DC Hipot Testing Device
HZZGF 80kV 5mA DC Hipot Testing Device
Product Overview
The HZZGF 80kV 5mA DC hipot tester utilizes high-frequency pulse width modulation (PWM) technology to achieve closed-loop regulation, ensuring high voltage stability, low ripple factor, and fast, reliable protection circuitry.
The wide-temperature LCD screen features a green backlight, providing clear display in both bright light and complete darkness. High-voltage components are manufactured with Dupont new filling material, enhancing product stability and reliability.
These products are widely used as regulated DC high-voltage power supplies in electric power supply departments, power transmission and transformation engineering companies, preventive testing in large industrial enterprises, and scientific research institutes.
Technical Parameters
|
Voltage (KV)/mA Current (mA) |
Control Box |
High-Voltage Unit |
|||
|
Rated Voltage |
Size (mm) |
Weight kg |
Size (mm) |
Weight kg |
|
|
80/2-5 |
80KV |
310 * 250 * 230 |
6kg |
490*260*220 |
8kg |
Common Fault And Solution
|
fault phenomenon |
solution |
|
|
1 |
The power indicator light is on. |
Replace ACRD fuse. If burnout again, check whether the power supply is over 380v. If so, remove the varistor, then the product can be used for emergency. |
|
2 |
Green light is on but HV does not increase. |
Check if fast loading multi-core cable line 6 and 7 are disconnected. If HV increased suddenly after turning the knob clockwise for a few circles, then the problem lies in the fast loading multi-core cable. |
|
3 |
Adjusting knob is turned to zero and voltage-increasing switch is on, but there is no indicator light. |
Check if fast loading multi-core cable line 1 and 2 are disconnected. |
|
4 |
Voltage is increased but there is no display. |
Check if fast loading multi-core cable line 1 and 2 are disconnected. |
|
5 |
Current exists but there is no value display |
Check if fast loading multi-core cable line 3, 4 and 5 are disconnected. |
|
6 |
voltage display is unstable after voltage increase (non-capacitive test) |
Check if fast loading multi-core cable line 3, 4 and 5 are disconnected. |
|
7 |
Over current always appears in large capacitive tests |
Whether operation begins after green light for voltage increase is on. 2. Whether stop for 2 seconds at 3/4 circle. 3. Whether hv cable has short circuit to earth. |
|
8 |
Too much deviation for high and low terminal ammeters |
Whether low battery at high terminal ammeter. 2. Whether caused by corona. 3. Whether caused by insulation characters of flexible cable. |
|
9 |
No-load voltage increase, large current leakage. |
Too close to objects on the ground. Dirty insulating cylinder. Clean the cylinder surface. 3. Too large corona current. |
|
10 |
Unable to increase to rated voltage. |
Turn overvoltage knob clockwise to maximum |
|
11 |
unable to increase voltage, over-current always occurs |
Check whether ground wire is removed. Operation begins after green light for voltage increase is on. 3. Whether shielding wire of high voltage cable is grounded. |
|
12 |
High terminal micro ammeter is always zero. |
Whether the black line of shielding layer and the red line of core wire is connected. 2. Whether one side of the red clip is disconnected at the root. |
|
13 |
fast loading line is difficult to connect |
Check alignment pin Press and turn clockwise 3. Whether leading line inside socket is bent. |
|
14 |
Over-current occurs before reaching rated voltage. |
Check whether grounding wire is removed. Whether operation begins after green light for voltage increase is on. 3. Insufficient insulation distance causes discharge. |
|
15 |
Over-current often occurs during zinc oxide arrester tests. |
1. Whether caused by too rapid voltage increase at turning point. Adjust the knob slowly at turning point. |
|
16 |
Unstable current during capacitive tests. |
1.Whether caused by HV equipment to test 10 kV cable. 2. Sudden unstable currents are mostly caused by break of inner wire in fast loading multi-core cable. |
|
17 |
Voltage increases from non-zero state after turning knob clockwise |
Caused by inner shield of line 1 and 2, break of line 4 and 5 in fast loading multi-core cable |
|
18 |
Picture missing on LCD |
Partial damage of LCD, return to factory for replacement. |
|
19 |
No current at rated voltage |
Check whether output core wire is broken |
|
20 |
Ammeter data exists in control box, but there is no current display |
The clip should be suspended in the air. |
Packing List
|
No. |
Item |
Qty |
|
1 |
Control Box |
1 |
|
2 |
High Voltage Line |
1 |
|
3 |
Power Line |
1 |
|
4 |
Control Line |
1 |
|
5 |
Ground Lead |
1 |
|
6 |
High Voltage Generator |
1 |
|
7 |
Discharge Rod |
1 |
|
8 |
Anti - Shock Ammeter |
1 |



Hot Tags: hzzgf 80kv 5ma dc hipot testing device, China, suppliers, manufacturers, price, for sale, 60kv dc hipot tester, 200kv 5ma dc hipot tester, 60kv 5ma hipot tester, dc hipot tester price, dc high voltage test for cables, dc withstand voltage tester