HZJQ-1 Transformer Oil BDV Test Kit 80kV 100kV
HZJQ-1 Transformer Oil BDV Test Kit 80kV 100kV




Summary
The HZJQ-1 transformer oil BDV test kit is a high-precision, all-digital industrial instrument developed by our scientific and technical team. Leveraging our expertise and conducting extensive field tests with long-term, unremitting efforts, we have designed this instrument in accordance with the relevant provisions of national standard GB 507-1986, industrial standard DL/T 846.7-2004, as well as ASTM D1816 and ASTM D877.
To meet the diverse needs of users, this series of instruments is available in multiple configurations, including single-cup, three-cup, and cup-type models. The instrument features a simple structure and an elegant appearance.
Features
Extended 100kV Range: Covers the full spectrum of insulating oil test requirements - from routine distribution transformer maintenance (typically 30–60kV) to acceptance testing of EHV transformer oil where standards call for 100kV withstand verification.
Fully Automated Workflow: Boosting → stirring → standing → breakdown detection → calculation → printing are all executed automatically after a single parameter setup, eliminating operator variability and reducing test time by up to 70% compared to manual ramp methods.
Built-In Safety: Over-voltage, over-current, and limit protection circuits safeguard the operator during every test. High-voltage energizes only when the oil cup cover is fully closed.
Field-Ready Documentation: The integrated thermal printer produces an immediate hardcopy of each individual breakdown value and the calculated average - ready for maintenance records, audit trails, and customer reports.

Major Factor
| Parameter | Specification |
| Output Voltage | 0~80 kV (100 kV optional) |
| Voltage Distortion Rate | <3% |
| Voltage Raising Speed | 0.5~5 kV/s (adjustable) |
| Standing Time | 15 min (adjustable) |
| Boosting Interval | 5 min (adjustable) |
| Boosting Frequency | 1~9 times (optional) |
| Booster Capacity | 1.5 kVA |
| Measuring Accuracy | ±3% |

FAQ
Q1: 100kV vs standard 80kV BDV testers? 100kV covers EHV oil, esters, 100kV protocols.
Q2: How many breakdown tests per sample? Average? 1–6 tests; auto mean. 6 per IEC 60156.
Q3: How to clean the oil cup? Silk cloth, 2.5mm gap, ether×3, sample rinse.
Q4: No breakdown at maximum voltage? Display ">100kV". Re-check gap, clean, sample.
Q5: Common faults and how to fix them? Check power, connectors, contrast, printer cables.



Hot Tags: HZJQ-1 Transformer Oil BDV Test Kit 80kV 100kV, China, suppliers, manufacturers, price, for sale, Insulating oil bdv tester, 100 kv oil vbd test, dielectric oil tester 60 kv, transformer oil bdv test device, bdv test kit 60kv, iec 60156, BDV Measuring Kit, 60kv 80kv portable transformer oil bdv tester hzjq-1, oil insulation test kit, OIL CAP FOR 100KV TRANSFORMER OIL BDV TESTER, 80 kv auto portable oil test, 90kV Liquid Dielectric Breakdown Tester, oil insulation test kit 100kv, huazheng bdv 80kv, insulating oil test kit 100kv bdv, fully automatic transformer oil testing kit tool, portable bdv measuring kit, bdv test kit specification, dielectric strength bdv testing kit, Transformer Oil Breakdown Voltage Test Set, bdv testing kit, bdv oil testing machine, transformer oil test device, insulating oil analyzer equipment, insulating oil dielectric strength tester