
200kv 10kVA AC DC Hv Automatic Sf6 Inflatable Test Transformer
2) Please discharge the sample object if the sample object is a capacitive equipment.
Product Introduction
We have the most advanced production equipment, experienced and qualified engineers and workers, recognized quality control systems and a friendly professional sales team pre/after-sales support for Manufacturing Companies for sf6 gas moisture analyzer, turns ratio test equipment, battery discharge machine. For our company's professional team, we continue to develop new ideas to manage and motivate them. We hope to establish a modern talent system and create a strong international level of modern corporate talent. We actively undertake social responsibility and contribute to social development, which reflects our responsibility and commitment. We insist on improving the existing production process and eliminating the unstable factors in the production process.
HZQ AC Hipot SF6 Gas Inflated Type Power Frequency Testing Transformer

Technical parameters of HZQ series alternating current test transformers
Model | Capacity (KVA) | High Frequency Voltage | High Frequency | Low Frequency Voltage input | |
V | A | ||||
HZQ-1.5 | 1.5 | 50 | 30 | 200 | 7.5 |
HZQ -3 | 3 | 50 | 60 | 200 | 15 |
HZQ -5 | 5 | 50 | 100 | 200 | 25 |
HZQ -10 | 10 | 50 | 200 | 230/400 | 50/26 |
HZQ -20 | 20 | 50 | 400 | 380 | 53 |
HZQ-30 | 30 | 50 | 600 | 380 | 79 |
HZQ -40 | 40 | 50 | 800 | 380 | 105 |
HZQ -50 | 50 | 50 | 1000 | 380 | 132 |
HZQ-5 | 5 | 100 | 50 | 200 | 25 |
HZQ -10 | 10 | 100 | 100 | 200/380 | 50/26 |
HZQ -20 | 20 | 100 | 200 | 380 | 53 |
HZQ -30 | 30 | 100 | 300 | 380 | 79 |
HZQ-40 | 40 | 10 | 400 | 380 | 105 |
HZQ-50 | 50 | 100 | 500 | 380 | 132 |
HZQ-100 | 100 | 100 | 100 | 500 | 263 |
HZQ-150 | 150 | 100 | 1500 | 500 | 300 |
HZQ-200 | 200 | 100 | 2000 | 500 | 400 |
HZQ-250 | 250 | 100 | 2500 | 380 | 500 |
HZQ-20 | 20 | 150 | 133 | 380 | 53 |
HZQ-30 | 30 | 150 | 200 | 380 | 79 |
HZQ-50 | 50 | 150 | 333 | 380 | 132 |
HZQ-100 | 100 | 150 | 666 | 500 | 263 |
HZQ-150 | 150 | 150 | 1000 | 500 | 300 |
HZQ-200 | 200 | 150 | 1333 | 500 | 400 |
HZQ-250 | 250 | 150 | 1666 | 380 | 500 |
HZQ-30 | 30 | 200 | 150 | 380 | 79 |
HZQ-50 | 50 | 200 | 250 | 380 | 132 |
HZQ-100 | 100 | 200 | 500 | 380 | 263 |
HZQ-150 | 150 | 200 | 750 | 500 | 300 |
HZQ-200 | 200 | 200 | 1000 | 500 | 400 |
HZQ-250 | 250 | 200 | 1250 | 500 | 500 |
HZQ-30 | 30 | 250 | 120 | 380 | 79 |
HZQ-50 | 50 | 250 | 200 | 380 | 132 |
HZQ-100 | 100 | 250 | 400 | 380 | 263 |
HZQ-150 | 150 | 250 | 600 | 500 | 300 |
HZQ-200 | 200 | 250 | 800 | 500 | 400 |
HZQ-250 | 250 | 250 | 1000 | 500 | 500 |
The operation of the insulation test with HIPOT tester is as follows:
1) Please make grounding connection for sample object, HV transformer and main control box first
2) Please discharge the sample object if the sample object is a capacitive equipment.
3) Please make connection for tester and sample object according to figure 3.
4) Please make power connection for main control box.
5) Confirm the high voltage value in withstand.
6) Setting the protection value of current by the pointer on the over current protection relay panel.
7) Adjust the regulator to zero position and then press down the close button on the panel the tester with enable the high voltage output unit.
8) If the regulator is not at zero position when you press down the close button the high voltage output unit would not be enabled.
There is a zero position indicator light on the panel of the main control box.
9) Adjust the high voltage output to the withstand test value step by step. Read the high voltage value and LV current from meters at the same time.
10) Start the timer by the timer switcher on the main control box panel when the high voltage has.
11) If the current over the value set on the panel of the over current relay the tester would cut off the power supply of HV transformer immediately. It is said the test result is failure.
12) If the timer display value reach the set value the tester would have a sound alarm to inform operator that the withstand time is ok. If the tester has not start the over current protection unit before sound alarm it is said the test result is ok.
13) Open the power supply of HV transformer by press down the "open" button on the panel of the main control box when test is end.
14) Please discharge the high voltage circuit of sample equipment before remove off the cable connection of high voltage circuit.
Please do not start the test if some part of the tester had been destroyed.







We enhance the economic efficiency and technological development of our company by maintaining a high yield of our 200kv 10kVA AC DC Hv Automatic Sf6 Inflatable Test Transformer. Meanwhile, our access to a large range of factories, coupled with our excellent management, also ensures that we can quickly fill your requirements at the best prices, regardless the order size. We enhance our sense of self-discipline, consciously regulate internal behavior, and effectively focus on and strengthen internal management supervision.
Hot Tags: HZQ SF6 Inflated Type Electrical Testing Transformer, China, suppliers, manufacturers, price, for sale, Inflated Type High Potential Testing Transformer, Inflatable High Voltage Testing Transformer, AC DC Testing Transformer, SF6 Gas Insulated Inflatable Testing Transformer, HZQ, Cable testing transformer 3 kva, partial discharge testing, hzdl130 primary current injection tester, clamp on earth ground resistance tester, astm d1816 astm d877 oil breakdown voltage testing, aniline point test apparatus, distribution transformer test bench
[[ProKeywords]]SPEC DATA
Send Inquiry
