100kv AC DC High Voltage Testing Transformer Hv Inflatable Test Transformer
2) Please discharge the sample object if the sample object is a capacitive equipment.
Product Introduction
Compared with other similar products, our cable fault tester, density measuring devices, partial discharge detector has many advantages, such as stable performance and reasonable price, etc. Our company has strong technical force, sophisticated equipment, advanced testing methods, and superb production technology. Because of these, you will have no worries about choosing us. Our company has been taking quality reputation as the purpose, taking the market as the guidance, seeking development by innovation, and constantly develop new products. We always insist on customer-centered, hard-working as the basis, from the continuous innovation of customer needs, and won the respect and trust of customers.
HZQ AC Hipot SF6 Gas Inflated Type Power Frequency Testing Transformer

Technical parameters of HZQ series alternating current test transformers
Model | Capacity (KVA) | High Frequency Voltage | High Frequency | Low Frequency Voltage input | |
V | A | ||||
HZQ-1.5 | 1.5 | 50 | 30 | 200 | 7.5 |
HZQ -3 | 3 | 50 | 60 | 200 | 15 |
HZQ -5 | 5 | 50 | 100 | 200 | 25 |
HZQ -10 | 10 | 50 | 200 | 230/400 | 50/26 |
HZQ -20 | 20 | 50 | 400 | 380 | 53 |
HZQ-30 | 30 | 50 | 600 | 380 | 79 |
HZQ -40 | 40 | 50 | 800 | 380 | 105 |
HZQ -50 | 50 | 50 | 1000 | 380 | 132 |
HZQ-5 | 5 | 100 | 50 | 200 | 25 |
HZQ -10 | 10 | 100 | 100 | 200/380 | 50/26 |
HZQ -20 | 20 | 100 | 200 | 380 | 53 |
HZQ -30 | 30 | 100 | 300 | 380 | 79 |
HZQ-40 | 40 | 10 | 400 | 380 | 105 |
HZQ-50 | 50 | 100 | 500 | 380 | 132 |
HZQ-100 | 100 | 100 | 100 | 500 | 263 |
HZQ-150 | 150 | 100 | 1500 | 500 | 300 |
HZQ-200 | 200 | 100 | 2000 | 500 | 400 |
HZQ-250 | 250 | 100 | 2500 | 380 | 500 |
HZQ-20 | 20 | 150 | 133 | 380 | 53 |
HZQ-30 | 30 | 150 | 200 | 380 | 79 |
HZQ-50 | 50 | 150 | 333 | 380 | 132 |
HZQ-100 | 100 | 150 | 666 | 500 | 263 |
HZQ-150 | 150 | 150 | 1000 | 500 | 300 |
HZQ-200 | 200 | 150 | 1333 | 500 | 400 |
HZQ-250 | 250 | 150 | 1666 | 380 | 500 |
HZQ-30 | 30 | 200 | 150 | 380 | 79 |
HZQ-50 | 50 | 200 | 250 | 380 | 132 |
HZQ-100 | 100 | 200 | 500 | 380 | 263 |
HZQ-150 | 150 | 200 | 750 | 500 | 300 |
HZQ-200 | 200 | 200 | 1000 | 500 | 400 |
HZQ-250 | 250 | 200 | 1250 | 500 | 500 |
HZQ-30 | 30 | 250 | 120 | 380 | 79 |
HZQ-50 | 50 | 250 | 200 | 380 | 132 |
HZQ-100 | 100 | 250 | 400 | 380 | 263 |
HZQ-150 | 150 | 250 | 600 | 500 | 300 |
HZQ-200 | 200 | 250 | 800 | 500 | 400 |
HZQ-250 | 250 | 250 | 1000 | 500 | 500 |
The operation of the insulation test with HIPOT tester is as follows:
1) Please make grounding connection for sample object, HV transformer and main control box first
2) Please discharge the sample object if the sample object is a capacitive equipment.
3) Please make connection for tester and sample object according to figure 3.
4) Please make power connection for main control box.
5) Confirm the high voltage value in withstand.
6) Setting the protection value of current by the pointer on the over current protection relay panel.
7) Adjust the regulator to zero position and then press down the close button on the panel the tester with enable the high voltage output unit.
8) If the regulator is not at zero position when you press down the close button the high voltage output unit would not be enabled.
There is a zero position indicator light on the panel of the main control box.
9) Adjust the high voltage output to the withstand test value step by step. Read the high voltage value and LV current from meters at the same time.
10) Start the timer by the timer switcher on the main control box panel when the high voltage has.
11) If the current over the value set on the panel of the over current relay the tester would cut off the power supply of HV transformer immediately. It is said the test result is failure.
12) If the timer display value reach the set value the tester would have a sound alarm to inform operator that the withstand time is ok. If the tester has not start the over current protection unit before sound alarm it is said the test result is ok.
13) Open the power supply of HV transformer by press down the "open" button on the panel of the main control box when test is end.
14) Please discharge the high voltage circuit of sample equipment before remove off the cable connection of high voltage circuit.
Please do not start the test if some part of the tester had been destroyed.







We are committed to providing the most valuable 100kv AC DC High Voltage Testing Transformer Hv Inflatable Test Transformer and service solutions for all industries. We seek efficiency by quality and develop by technology. The needs of users are our pursuit. We always look at the quality of our products from the user's point of view.
Hot Tags: HZQ SF6 Inflated Type Electrical Testing Transformer, China, suppliers, manufacturers, price, for sale, Inflated Type High Potential Testing Transformer, Inflatable High Voltage Testing Transformer, AC DC Testing Transformer, SF6 Gas Insulated Inflatable Testing Transformer, HZQ, Cable testing transformer 3 kva, AC Withstand Voltage Test Platform, 20kv insulation resistance tester, 6 phase relay testing, three cups insulation oil analyzer, transformer oltc tester, capacitance and tan delta meter