+86-312-6775656
HZCR-5000 Smart Multi-function Power Quality Analyser

HZCR-5000 Smart Multi-function Power Quality Analyser

Three-phase power quality analyzer is a device used to analyze and monitor the power quality in a three-phase power system. It can measure parameters such as voltage, current, power factor, harmonics, voltage dips, etc. Usually composed of a display, data storage, measurement sensors, control...
Send Inquiry
Product Details ofHZCR-5000 Smart Multi-function Power Quality Analyser

Huazheng Electric Manufacturing (Baoding) Co., Ltd. is one of the leading manufacturers and suppliers of hzcr-5000 smart multi-function power quality analyser in China. Please feel free to buy high quality equipment for sale here from our factory. Good service and reasonable price are available.

 

HZCR-5000 Smart Multi-function Power Quality Analyser

 

A three-phase power quality analyzer is a device used to analyze and monitor power quality in three-phase power systems. It measures parameters such as voltage, current, power factor, harmonics, and voltage dips. The instrument typically consists of a display, data storage, measurement sensors, and control devices.

 

HZCR-5000 Power Quality Analyzer

General Specifications

Parameter Specification
Model HZCR-5000
Processor DSP (>200MHz) + ARM dual-core
ADC 2 × ADI AD7655, 16-bit, 4-channel synchronous, up to 1 MSPS
Voltage Channels 4U / 4I (4 voltage + 4 current)
Phase-to-Neutral Voltage 1.0V – 1,000V
Phase-to-Phase Voltage 1.0V – 2,000V
Current Range 10mA – 6,000A (via interchangeable clamps)
Frequency Range 40Hz – 70Hz
Harmonic Analysis Orders 1–50, voltage + current + apparent power
Voltage Accuracy (RMS) ±(0.5% + 5dgt)
Current Accuracy (RMS) ±(0.5% + 5dgt)
Active Power Accuracy ±(1% + 3dgt) @ cosφ ≥ 0.8; ±(1.5% + 10dgt) @ cosφ 0.2–0.8
Frequency Accuracy ±0.03Hz
Display 5.6-inch colour LCD, 640×480 pixels
Transient Records 150 sets (4-cycle waveform per event)
Inrush Current Capture 100 seconds continuous
Trend Recording 300 days (20 parameters at 5s interval); 2GB SD card
Alarm Log 12,800 entries; 40 configurable groups; 123 monitorable parameters
Screen Snapshots 60 images
Network Connections Single-phase, split-phase, 3-wire / 4-wire / 5-wire three-phase
Safety Standard IEC 61010 CAT.III 1000V / CAT.IV 600V; IEC61326; Pollution degree 2
Battery 9.6V Li-ion, 4,500 mAh, 8 hours continuous; charges via included mains adapter (AC 100–240V)
Communication USB (to PC via included software)
Operating Temperature –10°C to 40°C
Humidity < 80% RH
Dimensions 240 × 170 × 68 mm
Weight 1.6 kg (with battery)
Languages Chinese / English

hzcr-5000 power quality analyzer

The direction of the end of the current clamp with the same name is as follows:

The current clamp is marked with an arrow, and the direction of the arrow is the input side, which is the input end of the same direction as the current, that is, the end with the same name.

The S-008 current clamp is marked with an arrow, and the direction of the arrow is the input side, which is the same-direction input end of the current, that is, the end with the same name.

S-070, S-105, and S150 current clamps are marked with red arrows, and the direction of the arrow is the input side, which is the input end of the same direction as the current, that is, the end with the same name.

The S-200JF flexible coil current sensor is marked with a black arrow, and the direction of the arrow is the input side, which is the input end of the same direction as the current, that is, the end with the same name.

 

CE Certificate

B3384 EMC Certificate Power Quality Analyzer

How do I select the right current sensor and verify correct connection polarity?

Sensor selection: Match the expected maximum current to the sensor range - always use the smallest sensor whose range exceeds the maximum current. Using a 1,000A clamp on a 5A circuit gives poor resolution; using a 10A clamp on a 50A circuit will overrange the input.

Polarity identification (critical - reversed polarity causes incorrect power sign and phase angle):

10A clamp: the side with the red dot is the current non-inverting input (→ toward the load)

100A / 1,000A clamp: the side without screws is the current non-inverting input (→ toward the load)

6,000A Rogowski coil: the arrow icon (lock logo side) marks the current direction input

Quick polarity check: after connecting, display the phasor diagram. In a normal inductive load with correct connections, the current vector for each phase should lag its corresponding voltage vector by a small angle (0°–90°). If a current vector leads voltage or points in the opposite direction from the other phases, that CT is reversed.

lQDPKcrtGtmqmW_NAazNAyCw_iF2foFjEn0JNdw6T7ADAg_800_428

image012

image014

Request for quote_

Hot Tags: HZCR-5000 Smart Multi-function Power Quality Analyser, China, suppliers, manufacturers, price, for sale, power quality tester, 3 phase power quality analyzer price, 6000a measure current power quality analyzer, 3phase power quality analyzer, power quality analyzer with data logger, pqa analyzer

Send Inquiry

(0/10)

clearall