+86-312-6775656
Transformer Ratio Verification Device TTR Standard Calibrator

Transformer Ratio Verification Device TTR Standard Calibrator

Transformer Ratio Verification Device TTR Standard Calibrator I. Product Overview The Transformer Ratio & Vector Group Tester Calibration Device is a precision calibration standard developed for digital transformer testers. Compliant with GB1094.1-1996 ( Power Transformers – Part 1:...
Send Inquiry
Product Details ofTransformer Ratio Verification Device TTR Standard Calibrator

 

Transformer Ratio Verification Device TTR Standard Calibrator

 

I. Product Overview

The Transformer Ratio & Vector Group Tester Calibration Device is a precision calibration standard developed for digital transformer testers. Compliant with GB1094.1-1996 (Power Transformers – Part 1: General) and JJG314-2010 (Measuring Voltage Transformers), it provides traceable calibration for ratio and vector group measurements.

 

Core Features

High-Voltage Operation

Supports calibration at 200V input voltage.

Flexible Ratio Setting

7-decade adjustment dials enable any ratio value from 1.000000 to 100,000.

Vector Group Simulation

Configures all standard connections: D/d, D/y, D/z, Y/d, Y/y, Y/z.

Passive Design

Three single-phase ratio standards combined via switches, ensuring high stability and anti-interference capability.

 

II. Technical Specifications

1. General Performance

Parameter Value
Ratio Accuracy Class 0.005
Input Voltage 0–240 V (Ratio Calibration)
0–250 V (Vector Group Verification)
Ratio Range 1.000000–100,000

2. Vector Group Output

Connection Ratio Base Values Calculation Rule
Y/Y, D/D 10, 100, 1000 Base ratio
Y/D 17.732, 173.2, 1732 Base ratio × √3
D/Y 5.7735, 57.735, 577.35 Base ratio ÷ √3
Y/Z 5.7735, 57.735, 577.35 Base ratio ÷ √3
D/Z 3.3333, 33.333, 333.33 Base ratio ÷ 3

Output Ratio Accuracy: ±0.05%

 

III. Operation Notes

Calibration Procedure

Set the vector group switch before applying voltage.

Do not modify connections or switch settings during calibration.

Voltage Limits

Max input voltage: 240 V (ratio calibration) / 250 V (vector group verification).

Maintenance Warning

Unauthorized disassembly voids warranty. Contact the manufacturer for malfunctions.

 