+86-312-6775656

XZTZ2000 Series Clamp Ground Resistance Tester

Mar 01, 2025

XZTZ2000 Series Clamp Ground Resistance Tester

2

Introduction

Clamp ground resistance tester, also known as loop resistance tester, is used to test ground resistance. This instrument uses a new black luxury screen design, the resistance current is displayed on the same screen, and it also has functions such as data storage, data review, alarm, and automatic shutdown. The whole machine is beautiful and high-grade, with a wide range, high resolution, convenient operation, convenient carrying, accurate, reliable, stable performance and strong anti-interference ability. Moreover, it has a shock-proof, dust-proof and moisture-proof structure. It is a common and indispensable instrument for telecommunications, electricity, meteorology, computer rooms, oil fields, electromechanical installation and maintenance, and industrial enterprises that use electricity as industrial power or energy. It is suitable for measuring grounding resistance of various telecommunications, electric power, meteorology, computer room, oil field, power distribution lines, tower transmission lines, gas stations, factory grounding grids, lightning rods, etc.

The clamp ground resistance tester is controlled by a microprocessor and can accurately detect ground resistance. It uses fast filtering techniques to minimize interference. Simultaneous data storage and data upload functions.

 

Model parameters

Model

Resistance Range

Current Range

XZTZ2000A+

0.01Ω-200Ω

--

XZTZ2000+

0.01Ω- 500Ω

--

XZTZ2000C+

0.01Ω-1200Ω

0.00mA-20A

XZTZ2000B+Explosion-proof

0.01Ω-1200Ω

 

 

Range and Accuracy

Measurement Mode

Measuring Range

Resolution

Accuracy

Resistance

0.010Ω-0.099Ω

0.001Ω

±(1%+0.01Ω)

0.10Ω-0.99Ω

0.01Ω

±(1%+0.01Ω)

1.0Ω-49.9Ω

0.1Ω

±(1%+0.1Ω)

50.0Ω-99.5Ω

0.5Ω

±(1.5%+0.5Ω)

100Ω-199Ω

±(2%+1Ω)

200Ω-395Ω

±(5%+5Ω)

400-590Ω

10Ω

±(10%+10Ω)

600Ω-880Ω

20Ω

±(20%+20Ω)

900Ω-1200Ω

30Ω

±(25%+30Ω)

*Current

0.00mA -9.95mA

0.01mA

±(2.5%+1mA)

10.0mA -99.0mA

0.1mA

±(2.5%+5mA)

100mA -300mA

1mA

±(2.5%+10mA)

0.30A-2.99A

0.01A

±(2.5%+0.1A)

3.0A-9.9A

0.1A

±(2.5%+0.3A)

10.0A-20.0A

0.1 A

±(2.5%+0.5A)

*Only available for instruments with current function