XZTY8600A Leakage Protector(RCD) Tester

Jun 26, 2025

XZTY8600A Leakage Protector(RCD) Tester

 

Introduction

XZTY8600A Leakage Protector(RCD) Tester is designed to test the leakage initiating separation time, line AC voltageof various leakage protectors online, the test current from 3~500mA with 18 grade (3mA,5mA,7mA,10mA,15mA,20mA,30mA,35mA,50mA,100mA,125mA,150mA,175mA,250mA,275mA,300mA,375mA,500mA), the leakage initiating time range is 0~999ms, AC voltage range: 0~600V.

The tester equip with large LCD displayer, white screen backlight, bar disgram indication. Output current, initiating time, battery power and phase are displayed on the same screen, with the functions of automatic shutdown, setting fault voltage indication, phase selection, backlight selection, data storage, etc. The tester operate easy, with high precision, small size, light weight, delicate appearance and easy to carry, the tester is an ideal tool for on-site or indoor detection of various leakage protectors.

Model Comparison

Model

Leakage Current Gear

Leakage Initiating Time Range

AC Voltage Range

Charge Function

Characteristic

XZTY8600

15~500mA

0~999ms

Non

Non

Portable

Measure leakage initiating time

XZTY8600A

3~500mA

0~999ms

0~280V

Non

Supper large LED screen

Measure leakage initiating time

XZTY8600B

5~1000mA

0~999ms

0~00V

Yes

Touch colorful screen, Measure leakage initiating time

 

 

Technical Specification

Function

Test leakage initiating time and line AC voltage of virous leakage protector

Power Supply

DC 9V(Alkaline dry cell R14 1.5V*6PCS

Rated Voltage

AC 220V

Leakage Current Gears

3mA,5mA,7mA,10mA,15mA,20mA,30mA,35mA,50mA,100mA,125mA,150mA,175mA,250mA,275mA,300mA,375mA,500mA

Current Accuracy

±10%rgt±5dgt

Rotary Knob Gear

OFF; V; X1; X2;X3; Auto (6gears)

Test Mode

Manual:

X1(3mA,5mA,7mA,10mA,15mA,20mA)

X2(30mA,35mA,50mA,100mA,125mA,150mA)

X3(175mA,250mA,275mA,300mA,375mA,500mA)

Auto: 3mA~500mA

Leakage Initiating Time Range

0~999ms.

Leakage Initiating Time Accuracy

5%rgt±3%dgt

AC Voltage Range

0~600V

AC Voltage Accuracy

±2rgt%±5dgt

Phase Select

0°/ 180°

Data Hold

After testing finish, the interface will hold the test result automatic

Failure Information Indication

LCD display "999" over time indication, it is possible that the rated initiating current grade of tested is too small or the leakage protector is faulty.

Test Wire Length

1.5M

Display Mode

4-digital large LCD display, white screen backlight

Teter Dimension

215mm×178mm×83mm

Tester Weight

Host: 955g(with battery); Total weight: 2kg(include all accessories)

Battery Voltage

news-256-163When the battery voltage lower than 7.4V, low battery voltage symbol" " display, and remind to replace the battery

Working Current

100mA Max

Working Temperature

-10℃-40℃, below 80%rh.

Storage Temperature

-10℃-60℃, below 70%rh.

Insulation Strength

≥100MΩ, AC 2kV/rms (between the shell and the screw).

Suitable Safety Standard

IEC1010-1, IEC1010-2-032, Pollution degree 2, CAT III(600V) IEC61326 (EMC standard).