XZTY8600A Leakage Protector(RCD) Tester
Introduction
XZTY8600A Leakage Protector(RCD) Tester is designed to test the leakage initiating separation time, line AC voltageof various leakage protectors online, the test current from 3~500mA with 18 grade (3mA,5mA,7mA,10mA,15mA,20mA,30mA,35mA,50mA,100mA,125mA,150mA,175mA,250mA,275mA,300mA,375mA,500mA), the leakage initiating time range is 0~999ms, AC voltage range: 0~600V.
The tester equip with large LCD displayer, white screen backlight, bar disgram indication. Output current, initiating time, battery power and phase are displayed on the same screen, with the functions of automatic shutdown, setting fault voltage indication, phase selection, backlight selection, data storage, etc. The tester operate easy, with high precision, small size, light weight, delicate appearance and easy to carry, the tester is an ideal tool for on-site or indoor detection of various leakage protectors.
Model Comparison
|
Model |
Leakage Current Gear |
Leakage Initiating Time Range |
AC Voltage Range |
Charge Function |
Characteristic |
|
XZTY8600 |
15~500mA |
0~999ms |
Non |
Non |
Portable Measure leakage initiating time |
|
XZTY8600A |
3~500mA |
0~999ms |
0~280V |
Non |
Supper large LED screen Measure leakage initiating time |
|
XZTY8600B |
5~1000mA |
0~999ms |
0~00V |
Yes |
Touch colorful screen, Measure leakage initiating time |
Technical Specification
|
Function |
Test leakage initiating time and line AC voltage of virous leakage protector |
|
Power Supply |
DC 9V(Alkaline dry cell R14 1.5V*6PCS |
|
Rated Voltage |
AC 220V |
|
Leakage Current Gears |
3mA,5mA,7mA,10mA,15mA,20mA,30mA,35mA,50mA,100mA,125mA,150mA,175mA,250mA,275mA,300mA,375mA,500mA |
|
Current Accuracy |
±10%rgt±5dgt |
|
Rotary Knob Gear |
OFF; V; X1; X2;X3; Auto (6gears) |
|
Test Mode |
Manual: X1(3mA,5mA,7mA,10mA,15mA,20mA) X2(30mA,35mA,50mA,100mA,125mA,150mA) X3(175mA,250mA,275mA,300mA,375mA,500mA) Auto: 3mA~500mA |
|
Leakage Initiating Time Range |
0~999ms. |
|
Leakage Initiating Time Accuracy |
5%rgt±3%dgt |
|
AC Voltage Range |
0~600V |
|
AC Voltage Accuracy |
±2rgt%±5dgt |
|
Phase Select |
0°/ 180° |
|
Data Hold |
After testing finish, the interface will hold the test result automatic |
|
Failure Information Indication |
LCD display "999" over time indication, it is possible that the rated initiating current grade of tested is too small or the leakage protector is faulty. |
|
Test Wire Length |
1.5M |
|
Display Mode |
4-digital large LCD display, white screen backlight |
|
Teter Dimension |
215mm×178mm×83mm |
|
Tester Weight |
Host: 955g(with battery); Total weight: 2kg(include all accessories) |
|
Battery Voltage |
|
|
Working Current |
100mA Max |
|
Working Temperature |
-10℃-40℃, below 80%rh. |
|
Storage Temperature |
-10℃-60℃, below 70%rh. |
|
Insulation Strength |
≥100MΩ, AC 2kV/rms (between the shell and the screw). |
|
Suitable Safety Standard |
IEC1010-1, IEC1010-2-032, Pollution degree 2, CAT III(600V) IEC61326 (EMC standard). |

When the battery voltage lower than 7.4V, low battery voltage symbol" " display, and remind to replace the battery