+86-312-6775656

HZDPS-30KV 30kV VLF Hipot Tester With Tangent Delta Test Function

May 16, 2024

HZDPS-30KV 30kV VLF Hipot Tester

 

Product Description

The high voltage withstand voltage test of electrical equipment is one of the most important items stipulated in the "insulation preventive test". Withstand voltage test can be divided into AC voltage withstand test and DC voltage withstand test, AC voltage test can be divided into power frequency, frequency conversion and 0.1Hz ultra-low frequency dielectric loss test technology, of which 0.1Hz ultra-low frequency dielectric loss technology is the latest technology, which also is the current International Electrotechnical Commission recommended technology.Our company's new generation of this series of VLF hipot tan delta generator adopt the latest American technology self-developed core products, using 7 inch touch screen, the latest ARM7 microcontroller, high-speed AD acquisition circuit, and equipped with background management software.It overcomes many of the shortcomings of similar domestic products (see Table 1), the cost performance is much higher than that of similar imported products, especially suitable for electrical equipment with large insulation equivalent capacitance (such as power cables, power capacitors, large and medium-sized generators and motors, etc.) voltage test. In line with the new national power industry standard in 2004 "Ultra-low frequency high voltage generator general technical conditions DL/T849.4-2004" requirements.

 

Technical Parameters Of HZDPS Series

1.Voltage(Peak): 0-30kv, Sensitivity: 0.1kV, Accuracy: 1 %

2.Waveform: Ultra-low frequency sine wave, DC voltage, Voltage positive and negative peak error: ≤3%, Voltage waveform distortion: ≤1%

3.Frequency range:0.1 Hz 0.05 Hz 0.02 Hz, Load range(Ultra-low frequency test): 0nF–10μF

4.Current: Measurement range: 0–70 mA, Sensitivity: 1μA, Accuracy: 1 %

5.Tan Delta:

Ultra-low frequency sine wave voltage range: 1–30 kVrms

Load range: 50nF–5μF

Resolution: ≥1x10-6

Accuracy: ≥1x10-3

Measurement range: 1x10-3–21000x10-3

Tan Delta measurement frequency: 0.1Hz

Capacitance range: 50nF-5μF

Resistance value rang: 30MΩ-10GΩ

Dimensions: 48cm*28cm*58cm

Weight: 45kg

6.Working condition: indoor,outdoor; Temperature: -10℃~+40℃; Humidity:≤85%RH

7.Power supply: Frequency 50Hz,60hz, Voltage 100v -260V±5%.

8.USB communication port.

9.Power supply fuse pipe: see Table 3

10.Power supply: Voltage 220V±5%, 50±5Hz

Calculation formula: I=2πfCU

 

Product Characteristics

☆ Advanced technology: Adopt digital frequency conversion technology, microcomputer control, boost, buck, measurement, protection and other test process fully automated.

☆ Equipment operation: simple wiring, easy to use.

☆ Comprehensive protection: multiple protection (overvoltage protection, HV and LV side overcurrent protection), quick action (action time ≤10ms), which is safe and reliable.

☆ Safe and reliable: LV connection between controller and high voltage generator, photoelectric control, ensure safe and reliable use.

☆ The high and low voltage closed loop negative feedback control circuit is adopted, and the output has no capacity rise effect.

☆ Complete configuration: capacitive touch screen, LCD English character display, automatic storage, automatic printing.

☆ Wide measurement range: 0.1Hz,0.05Hz ,0.02Hz multi-frequency selection, wide test range.

☆ Chinese-English shift and USB function

Send Inquiry