SBW-30KVA 30kW Three Phase Voltage Stabilizer
AC voltage stabilizer is developed by our company according to the load characteristics and designed for stable AC voltage. When the external power supply network voltage fluctuates or the load changes cause voltage fluctuations, and output voltage is automatically kept stable. This special voltage stabilizer has the characteristics of large capacity, high efficiency, small waveform distortion, stable voltage adjustment, etc., and it is suitable for a wide range of loads, can withstand instant overload, can work continuously for a long time, and can be switched by manual and automatic control. It has automatic protection devices for overvoltage and over current, easy to use and install, and reliable in operation.
|
Input |
Voltage regulation range |
3φ4W+G 380V±20% Line voltage 178-263V |
|
Frequency |
50Hz/60Hz |
|
|
Output |
Rated Capacity |
30KVA |
|
Rated current |
45A |
|
|
Rated voltage |
3φ4W+G 380V,1φ2W+G 220V |
|
|
Stabilization accuracy |
±1- 5%(Can be set) |
|
|
Response time |
≦1s |
|
|
Waveform distortion |
No additional waveform distortion (static) |
|
|
Efficiency |
≥98% |
|
|
Sampling method |
Isolated true effective value sampling |
|
|
Control protection |
Over-voltage |
Output phase voltage exceeds 10% (245V), cut off the output |
|
Under-voltage |
Output phase voltage is lower than 10% (195V), cut off the output |
|
|
Lack of phase |
Available (automatically cut off) |
|
|
overload |
Overload cuts off the output within 3 minutes |
|
|
Over-current |
Circuit breaker protection |
|
|
Short circuit |
Circuit breaker protection |
|
|
Bypass |
Manual bypass |
|
|
Indication |
Voltage |
A, B, and C three phases have true effective value LCD liquid crystal display |
|
Current |
A, B, and C three phases have true effective value LCD liquid crystal display |
|
|
Working status |
Voltage stabilization status/mains power status |
|
|
Abnormal |
||
|
Way of working |
It has two working modes: voltage stabilization and mains power |
|
|
Overload capacity |
5 times the rated current for 1 second |
|
|
Working pressure |
No breakdown within 1 minute at 3000V |
|
|
Ambient temperature |
-150C~450C |
|
|
environment humidity |
≤95%, no condensation |
|
|
Insulation resistance |
≥5MΩ |
|
|
cooling method |
Self-cooling |
|