1) Product apply range and features
1. 150kV power cable test
Capacitance to be tested: frequency at 30-300HZ, capacitance to bestested 0.35uF.
The test voltage is no more than 150kV, and the running time is 60min.
2. 150kV HV switch GIS test
Capacitance to be tested: frequency at 30-300HZ, capacitance to betested: 0.0885uF.
The test voltage is no more than 300kV, and the running time is 1min.
3. 28KV/800MVA generator test
Capacitance to be tested: frequency at 30-300HZ, capacitance to bestested 0.35uF.
The test voltage is no more than 59kV, and the running time is 1min.
 
2) Working environment
1. Ambient temperature: -15 0C -50 0C;
2. Relative humidity: ≤ 95% RH;
3. Altitude: ≤1000 m;
 
 
3)Operation condition
1. Rated capacity: 1500kVA;
2. Input power: three-phase 380V voltage, 50Hz frequency;
3. Rated voltage: 150kV; 300 kv
4. Rated current: 10A; 5 A
5. Working frequency: 30-300hz;
6. Device output waveform: sine wave
7. Waveform distortion rate: Output voltage waveform distortion rate ≤
1%;
8. Working time: allowed for 90min continuously under the rated
load; ;Overpressure 1.1 times 1 minute;
9. Temperature rise: after running 90min under rated load, the temperature
rise is ≤25K;
10. Quality factors: the device itself Q ≥ 30 (f = 45Hz);
11. Protection function: the test product has over-current, overvoltage and
test flashover protection (see the variable frequency power section);
12. Measurement accuracy: system RMS 1.5;