HZSF-702 High Precision SF6 Gas Dew Point Tester

Mar 16, 2024

HZSF-702 High Precision SF6 Gas Dew Point Tester

sf6 gas dew point tester

Technical Characteristics And Parameters

Features

Smart calibration

The sensor probe can automatically calibrate the zero point to ensure the readiness for each measurement;​

Quick and gas-saving

After turning on the machine and entering the measurement state, the dew point measurement time for each SF6 air barrier is about 5 minutes;

Safe and reliable

It adopts self-locking joints imported from Germany, which are safe, reliable and airtight;

Mass storage

Adopting a large-capacity data storage design, it can store up to 250 sets of test data;

High definition display

Color screen directly display dew point, moisture, temperature, humidity, time, date and dew point curve;

Moving measurement

Built-in large capacity rechargeable lithium battery, a full charge can work for 10 hours;

Accurate measurement

The temperature compensation function is added to ensure the accuracy of the measurement results under various temperature conditions.

Local calibration

This machine comes with calibration function, do not need to connect the computer to complete the data calibration.

Technical parameter

dew-point

Measuring range

-60℃~+ 20℃

measurement accuracy

±1℃

ambient temperature

-40℃~+80℃

environment humidity

0~100% RH

Display device

4.3-inch color touch screen

power supply

AC 220V;Built-in rechargeable battery: can be used for more than 10 hours on a single charge

weight

4.5Kg

size

300 mm×150 mm×300mm

Operating temperature

-30℃~+60℃

 

Measurement Methods

1,Connect SF6 devices

Connect the threaded end of the measuring pipe to the switch joint, tighten it with a wrench, and close the needle valve at the other end of the measuring pipe; insert one end of the quick connector on the measuring pipe into the air inlet of the instrument; insert one end of the exhaust pipe The exhaust port on the back of the instrument, and put the other end into a trench or window. Finally, connect the switch connector to the SF6 electrical equipment measurement interface and tighten with a wrench;

2,initialization

Turn on the power switch of the instrument, and the instrument will enter the initialization self-calibration process. After the calibration, it will automatically enter the measurement page.

3,Check battery

It is recommended to use DC power first for this instrument. When using DC power, please check the battery power displayed in the upper right corner. If the power indicator turns red, please turn off the phone and charge before continuing to use it.

4,Start measuring

Fully open the flow valve on the front panel of the dew point meter, and then slowly adjust the flow to about 0.5L/M by adjusting the needle valve on the measurement pipe to start measuring the SF6 dew point. The first device takes 5 to 10 minutes to measure, and each subsequent device takes 3 to 5 minutes.

5,Storing data

After the measurement is completed, the data can be saved in the instrument and press the "OK" key to bring up the operation menu. See the next section for specific operation methods.

6,Measure other equipment

After the measurement of a piece of equipment is completed, close the needle valve on the measuring pipe. Remove the switch connector together with the measuring pipe from the SF6 electrical device. If you need to continue measuring other devices, please do not turn off the instrument power and follow the steps above to continue measuring the next device.

7,Measurement ended

After all equipment measurements are completed, turn off the instrument power.