HZSF-521 SF6 Gas Decomposition Products Analyzer
I. Overview
SF6 decomposition detector produced by the company is intelligent, with high sensitivity, stability and convenient operation. It can automatically diagnose and put forward treatment Suggestions according to the detected concentration, providing a simple and effective means for the early detection of internal faults of SF6 electrical equipment.
II. Main technical indexes
1. Minimum detection quantity: 0.1 PPM
2. Stability: When the temperature changes from 20℃ to 40℃, the maximum drift of zero point ≤±0.1ppm
3. Accuracy: When measuring ≤2ppm, the error ≤±0.1ppm
When > 2ppm was measured, the error was ≤±0.2ppm
4. Repeatability: SO2 and H2S are ≤2%
5. Measurement range: 0~100ppm (customizable)
6. Temperature range: -40℃~+50 ℃
7. Humidity range: ≤95%RH
8. Atmospheric pressure: 86kPa~106kPa
9. Self-contained power supply: built-in rechargeable battery, which can work continuously for more than 10 hours after being fully charged
10. Shape: 252×310×98mm
11. Weight: 2.5kG
12. Communication: RS232
Main functions and characteristics
SF6 decomposition detector can quickly detect and judge the early faults inside SF6 electrical equipment (circuit breaker, transformer, TRANSFORMER, GIS and bushing, etc.) in the field by simultaneously monitoring SO2 and H2S decomposition products.
This instrument can be widely used in SF6 electrical equipment in electric power, railway, metallurgical and petrochemical industries.
SF6 electrical equipment internal gas by the pressure reducing valve, airway after entering instruments, two road into the SO2 and H2S sensor for testing at the same time, the SO2 and H2S concentration into corresponding electrical signal, through the operational amplifier, filter circuit, sent to the microprocessor and A/D converter, the analog signal is converted into the corresponding digital signals, the LCD display detection concentration of actual value.The memory number can be compared by the microprocessor logic with the expert diagnosis system to determine the type of fault.