HZRC9000B High/Low Voltage Clamp Meter

Nov 11, 2025

HZRC9000B High/Low Voltage Clamp Meter

 

I . Brief Introduction

HZRC9000B Series H/L Voltage Clamp Meter has broken through the traditional structure, which is specially well-designed for measuring high voltage current, adopting the latest CT technology and integrated mask digital technology, formed by composition of a special use clamp meter with a high-voltage insulation rod, as to HZCR9000B type --- wireless transmission of test data, it is equipped with wireless receivers, which can receive measured data within 30 meters line. If not using an insulation rod, it can be also used as a high precision low-voltage clamp meter, or an alternating current meter, which can accurately measure 0.01mA of current or leakage current.

HZRC9000B Series H/L Voltage Clamp Meter has an innovative integrated design between transducer clamp and transducer domain, ensuring the high-precision, high-reliability, and high-stability on constant test perennially.

HZRC9000B Series H/L Voltage Clamp Meter is connected with insulation rod, which can be used for measuring high voltage current that is below 60KV, on-line current measurement, also having peak maintenance, data preservation, data storage, wireless transmission and other functions, and its special clamp meter can make it easier for clamping or evacuating the tested wire through pressing or pulling back the insulation rod, time-saving and fast, widely used in transformer substation, power plant, industrial and mining enterprises as well as the inspection station and electrician maintenance departments for electrical current detection and field electrical operations. It can also replace the H/L voltage transforming ratio tester, that is, to detect the high and low current for primary circuit and secondary circuit separately, and then calculate to conclude the change of high and low pressure. The insulation rod is light and convenient, with the advantages of anti-moisture, high temperature resistance, anti-impact, bending resistance, high insulation, flexibility and other characteristics.

 

II.Series Model

Model

Range of measurement

Accuracy

Jaw Specification

Description

HZRC 9000

0.00mA-1200A

0.01mA

φ48mm

base

HZRC9000B

0.00mA-1200A

0.01mA

φ48mm

wireless

III.Technical Specification

Function

High voltage AC current measurement, low voltage AC current, leakage current measurement, on-line AC current supervision.

Power Supply

DC6V Alkaline Dry Battery (1.5V AAA X 4)

Test Method

Clamp CT, Integral Method

*Transmission Method

B Model: Wireless Transmission, the maximum distance for direct transmission is about 30m.

Display Mode

4 digital LCD display, backlight function, suitable for dark place.

LCD Dimension

47mm×28.5mm

Meter Dimension

W/H/T: 76mm×255mm×31mm

Clamp Diameter

φ48mm

Sampling Speed

About 2 times/second

Range of measurement

0.00mA~1200A(50/60Hz Auto Identification)

Resolution

0.01mA

Shift

0.0mA~1200A Automatic Shift

Test Accuracy(23℃±5℃,Below 80%RH)

0.0mA~299mA: ±1%±3dgt

0.30A~49.9A: ±1.5%±5dgt

50.0A~199.9A: ±2.0%±5dgt

200A~600A: ±3%±5dgt

601A~1200A: ±4%±5dgt

Data Storage

99 Groups, during storage, the symbol "MEM" gives indication, "FULL" mark will flash to indicate the memory has been full.

Circuit Voltage

Test for the circuit below 60KV (operated with insulation rod)

Peak Maintenance

Automatically maintain the height of the test value, usually in the test mode press PEAK key, PEAK lights, that is, to keep open the PEAK function, then press PEAK key to cancel this function

Data Preservation

Under general test mode, press HOLD button to preserve data, "HOLD" symbol display. then press HOLD Key to cancel this function

Data Access

"MR" symbol indicates, it can read the stored data by turning upwards and downwards.

Overflow Display

Exceed measurement range overflow function: "OL A" symbol display

* No signal Indication

When the receiver has not received transmit signal, it will display "no- -"symbol

Auto Shut Down

About 15 minutes after booting, the meter will shut down automatically, in order to decrease the battery consumption.

Battery Voltage

When the battery voltage is below 4.8V, the symbol of battery voltage" "will show to remind to replace battery.

Weight

Tester: About 335g (Including battery), total quality of meter: about 2.5Kg (including insulation rod and battery.)

Work Temperature and Humidity

-10°C ~40°C; Below 80%Rh

Storage Temperature and Humidity

-10°C ~60°C; Below 70%Rh

Insulated Rod Dimension

φ32mm,1m/Section(5 Sections)

Insulation Intension

AC 100KV/rms (Between insulation rod and clamp core)

Structure

Anti-Dripping Type II