+86-312-6775656

Huazheng HZTCW-300kVA/2×300kV Power Frequency Test Transformer Complete Test Device

May 07, 2024

Huazheng HZTCW-300kVA/2×300kV Power frequency test transformer complete test device

 

The complete set of 300kVA/2×300kV power frequency test transformer is suitable for testing products such as switches, bushings, transformers, transformers and insulators of 220kV and below for power frequency withstand voltage test and partial discharge measurement.

QQ20240507113300

Ⅱ Following the standard

JB/T9641-1999

Testing transformers

GB/T.311.1-1997

Insulation co-ordination for high voltage transmission and distribution equipment

GB/T16927.1-1997

High-voltage test techniques. Part 1: General test requirements

GB/T16927.2-1997

High-voltage test techniques. Part 2: Measuring systems

 

Ⅲ Composition of equipment

1.HZTCW-150/300-II power frequency series connecting test transformer superior, 1 set

2.HZTCW-300/300-I power frequency series connecting test transformer lower stage, 1 set

3.TYDZ-100/0-650 single-phase column voltage regulator, 1 set

4.GWC-300/600 power frequency capacitive voltage divider( Coupling capacitor), 1set

5.GR-0.5/600 power frequency protection resistor, 1set

6.HZ-AC20 power frequency console, 1 set

7.DGK-300KVA/600V compensation reactor, 1set

 

Ⅳ Technical parameters of main products

1.HZTCW-300/2×300 Power frequency test transformer of series connecting

Model number: HZTCW-300/2×300

Number of phases: single phase

Frequency: 50Hz

Rated capacity: 300KVA

Rated input voltage: 380V

Rated output voltage: 600KV

Rated input current: 500A

Rated output current: 0.5A

Impedance voltage: ≤15%

Waveform distortion rate: ≤5%

Unevenness of cascade voltage distribution of two transformers: ≤5%

Allowable running time: 30 minutes running at 100% rated voltage and 100% rated current; continuous running at 2/3 rated voltage and 2/3 rated current.

Partial discharge capacity: partial discharge capacity at 100% rated voltage <10PC, partial discharge capacity at 80% rated voltage <5PC.

2.TYDZ-100/0~650 single-phase column voltage regulator

Model number: TYDZ-300/0~600

Number of phases: single phase

Frequency: 50Hz

Rated capacity: 600KVA

Rated input voltage: 380V

Rated output voltage: 0-650V

Waveform distortion rate: ≤5%

Allowable running time: same as transformer

 

3.GWC-300/600 power frequency capacitive voltage divider(Coupling capacitor)

Model number: GWC-300/600

Rated frequency: 50Hz

Nominal capacity: 300PF±10%

Rated voltage: 600KV

Nominal partial pressure ratio: 1000:1

Dielectric loss: <0.5%

Measurement accuracy: 1%

Allowable running time: same as transformer

4.GR-0.5/600 power frequency protection resistor

Model number: GR-0.5/600

Rated frequency: 50Hz

Rated voltage: 600KV

Resistance value: 10KΩ

Rated current: 0.25A

Allowable running time: same as transformer

 

5.HZ-AC20 Power frequency console

Model number: HZ-AC20

Features:

(1) Capacitance voltage divider measurement voltmeter: accuracy 1%, with three and a half digits;

(2) The console is equipped with transformer input winding ammeter and voltmeter, and output winding ammeter.

(3) There is an overcurrent protection function in the console.

(4) The console is equipped with a pressure timer.

(5) The console has a zero protection function.

6.DGK-300/0.6 Compensation reactor

Model: DGK-300/0.6

Rated capacity: 300kVar

Rated current: 500A

Rated voltage: 0.6kV

Rated frequency: 50Hz

Allowable running time: same as transformer

Send Inquiry