1. Before testing with an insulation resistance tester, it is necessary to ensure that there is no electrical presence in the circuit being tested. Do not measure the insulation of live equipment or live lines. High voltage insulated gloves must be worn. When conducting insulation resistance testing, this instrument has dangerous voltage output. Be careful when operating to ensure that the tested object is firmly clamped and your hand is away from the test clamp. Then, press the test button to output high voltage. During the insulation impedance test, a beep may sound, but it is not a fault. Measuring capacitive loads takes a long time.
2. Do not take measurements when the battery cover is open. Do not short circuit two test probes in the high voltage output state, or measure the insulation resistance after the high voltage output. This improper operation can easily generate sparks and cause fire, and also damage the instrument itself. When the high voltage symbol is displayed or the buzzer emits a warning sound, measurements cannot be made even when the test button is pressed. Due to the different measured objects, their insulation resistance values may be unstable, which may result in unstable displayed resistance values.
3. When measuring insulation resistance, the test port voltage outputs from the positive (+) ground terminal to the negative (-) test terminal. When measuring, the grounding test wire is connected to the grounding terminal. Generally speaking, for insulation measurement to ground, when one end of the tested object is grounded, the method of connecting the grounding terminal to the positive electrode (+) results in a smaller resistance value, which is suitable for detecting insulation defects.
4. The instrument is equipped with automatic discharge function. After the measurement is completed, do not remove the test wire. Release the test button and let the instrument automatically release the voltage generated during the test. Please confirm that "0V" is displayed on the voltage monitor (auxiliary display zone 1) at this time. Do not touch the circuit immediately after the test is completed. The stored charges in the circuit may cause electric shock accidents.
5. Do not immediately remove the test wire. You must wait until the discharge is complete before touching the tested circuit. Switch to the "OFF" position and remove the test wire. Outside the "OFF" range, a current of 25mA is still required when not measured, and the automatic shutdown is about 3mA. When not using the instrument, please switch to the "OFF" position (less than 1uA