In the process of the management of the distribution room, whether the electrical equipment needs to do preventive tests, some managers may be confused. What are the advantages of doing preventive tests of electrical equipment? How long is the cycle? The following editor will help you understand each one.


1. Why do preventive tests of electrical equipment


Electrical preventive test is an important link in the operation and maintenance of power equipment, and it is one of the effective means to ensure the safe operation of power equipment.


Its purpose is to check whether electrical equipment is in good condition during long-term operation, and to grasp the insulation of electrical equipment, so that defects can be found and dealt with in a timely manner. The preventive test of electrical equipment plays a preventive role in preventing the power outage and serious damage to the equipment caused by the breakdown of electrical equipment under the action of working voltage or overvoltage.


Basis: In accordance with the national "Preventive Test Regulations for Power Equipment", the relevant industry standards, specifications and design materials for the inspection, testing or monitoring of the equipment.


2. What is a preventive test for electrical equipment


Whether it is high-voltage electrical equipment or live working safety appliances, they all have their own insulation structure. These equipment and appliances are subject to internal and external overvoltages that are much higher than the normal rated working voltage during operation, which may cause defects in the insulation structure and become latent failures.


On the other hand, along with the operation process, the insulation itself will also be degraded due to heat generation and aging under natural conditions.


Preventive test is a set of methods and methods for the diagnosis and testing of the insulation performance of the system to prevent accidents caused by changes in the insulation performance of electrical equipment in operation in response to these problems and possibilities.


3. The necessity of preventive test of power equipment


The necessity of the preventive test of electrical equipment is to avoid the breakdown of the equipment insulation of electrical equipment during operation and cause power outages, and to ensure the safe operation of the equipment.


This is not only for power equipment that has been put into operation, but also for newly built power equipment or equipment after major repairs, preventive testing is also very necessary.


4. Detection cycle


According to the national "Preventive Test Regulations for Power Equipment", the testing cycle of each equipment in the power distribution room is as follows:


1) High-voltage electrical equipment preventive test: 10KV indoor electrical equipment is tested every 1-2 years.


2) The 10KV arrester is tested once a year, and the general substation is required to be put into operation


3) 0.4KV arrester is tested once a year.


4) Power cable project: insulation resistance once a year.


5) Power transformer project: winding insulation resistance and absorption ratio once every two years.


6) Insulating tools (insulating shoes, insulating gloves, high-voltage test pencils, high-voltage insulating rods, etc.) are tested every six months.


7) Current transformer, voltage transformer project: winding insulation resistance and transformation ratio once every two years.


8) Oil switch project: insulation resistance once a year.


9) Relay protection device project: 10KV once every two years 