General technical requirements for the output voltage and waveform of the ultra-low frequency high voltage generator. The peak output voltage of the ultra-low frequency high voltage generator should be adjustable within the rated voltage range, and the output voltage and waveform should meet the following requirements:
1. The instability of the peak output voltage of the ultra-low frequency high voltage generator is less than 1%;
2. The frequency instability of the output voltage is less than 3%;
3. The waveform distortion rate of the output sine voltage is less than 5%;
4. The polarity conversion time of the output cosine square wave voltage does not exceed 10ms
5. The error of the positive/negative half-cycle of the output voltage of the ultra-low frequency high-voltage generator is less than 0.5s, and the peak deviation of the positive/negative half-wave is less than 5%.
Ultra-low frequency high voltage generator voltage instability test: The high voltage terminal of the ultra low frequency high voltage generator is connected to a capacitive load sample (such as a power capacitor) with a rated capacitance of 50%, and an external voltage measuring device with a comprehensive error of ≤1.0% is connected. When the measured high-voltage output voltage peak value gradually rises to 1.0 times the rated value within 60 minutes, the output voltage peak value is measured 10 times. After calculation, the instability of the peak output voltage should satisfy 1.
In the frequency stability test, the high-voltage terminal of the ultra-low frequency high-voltage generator is connected to a capacitive load sample (such as a power capacitor) with a rated capacitance of 50%, and an external voltage measuring device with a comprehensive error of ≤1.0% is connected. When the measured peak value of the high-voltage output voltage gradually rises to 1.0 times the rated value within 60 minutes, the output voltage frequency is measured 10 times. After calculation, the frequency instability of the output voltage should meet the requirements of 2.
In the sinusoidal voltage waveform distortion rate test, connect the high-voltage terminal of the ultra-low frequency high-voltage generator to a capacitive load sample with 50% of the rated capacitance (such as a power capacitor), and connect an external voltage measuring device with a comprehensive error of ≤1.5% to measure the high-voltage output voltage The output voltage waveform when the peak value gradually rises to 0.3, 0.5, 0.8, 1.0 times the rated value. The distortion rate of the sinusoidal voltage waveform output by the ultra-low frequency high voltage generator should meet 3.
In the cosine voltage polarity conversion time test, connect the high-voltage terminal of the ultra-low frequency high-voltage generator to a capacitive load sample (such as a power capacitor) with a capacitance of 50% of the rated capacitance, and connect a voltage measuring device with a comprehensive error of ≤1.5%. Measure the output voltage waveform when the peak value of the high-voltage output voltage gradually rises to 0.3, 0.5, 0.8, 1.0 times the rated value.