1. Test voltage
The AC voltage depends on the liquid to be measured, the electric field strength is between 0.03 kV/mm and 1 kV/mm, and a sinusoidal voltage with a frequency between 40 and 62 Hz is used.
2. Measurement
After the oil cup is filled with the oil sample, when the difference between the temperature of the inner electrode and the required test temperature is not greater than ±1℃, the measurement of the loss factor starts, and the voltage is only applied during the measurement. After completing the first measurement, pour out the oil sample and refill the oil cup with a second sample of the same oil. The procedure is the same as the first time, but the rinsing is omitted. Repeat the measurement after warming, and the difference between the two readings should not be greater than 0.010% plus 25% of the larger value of the two measurements.
If this requirement cannot be met, change the same oil sample again and do the test until the difference between the two adjacent readings does not exceed the sum of 0.010% and 25% of the larger value of the two measurements. At this time, the measured results are considered valid. .
Finally, take the lower of the two valid measurements as the loss factor for the liquid sample.
Common faults and solutions
1. When the machine is turned on, the indicator light of the power switch does not light up. Please check the fuse core of the power board to see if it is blown.
2. When the device is boosting the voltage, the LCD displays "electrode cup short circuit", please check whether the electrode cup is properly assembled.
3. When the device detects that the capacitance value of the empty cup deviates greatly from the standard value (60pF±5pF), please check whether the radio frequency head on the protective electrode cover of the power signal cable is loose.
4. When the device heats up, the temperature signal cannot be detected. Please check whether the temperature signal cable is connected correctly.
5. When the equipment does not heat up (that is, there is no special sound of intermediate frequency heating), please check whether the heating insurance is blown.