Some main factors affecting power frequency withstand voltage testing

May 21, 2024

1. We need to select testing equipment with appropriate capacity. If the capacity of the testing equipment is insufficient or too large, it will affect on-site testing.

2. The impact of altitude on testing requirements: As altitude increases, the spatial density decreases, the average free travel of electrons in the electric field increases, and electrons can collect more kinetic energy between two collisions (compared to normal density), which is more likely to cause ionization, resulting in a decrease in the discharge voltage of the air medium.

3. To prevent overvoltage during the testing process: If the voltage does not gradually increase from zero during the power frequency withstand voltage test, but rather the earth frame voltage on the primary winding of the test transformer appears on the test product, it is due to excitation surge overvoltage. If the power supply is suddenly cut off during testing, overvoltage may occur due to self induced potential for small capacity test samples. Both of the above situations may lead to accidental puncture of the test item. Therefore, when conducting power frequency withstand voltage tests, the testing operation rules should be strictly followed.

4. Impact of increased capacity on test values: In AC power frequency withstand voltage testing, the tested product is usually a capacitive load, and the high-voltage winding of the tested transformer is connected to the tested capacitor. In this way, the capacitive current flowing through the capacitive load will cause a voltage drop in the winding impedance of the test transformer, and the voltage on the secondary side of the test transformer will decrease, which is significantly higher than the calculated secondary side voltage. Conversion rate. This phenomenon is called the "capacity increase effect", and it can be seen that the original transformer ratio is not applicable. The increase process is directly proportional to the short-circuit impedance of the transformer, and the general increase range is about 4%-30%.

5. The impact of pressure waveform distortion on test results: Due to the presence of many nonlinear loads in the power unit, the number of harmonic circuit components increases, and the problem of voltage waveform distortion in the power grid is becoming more and more serious. In order to protect the accuracy of the test results, it is necessary to measure their peak value to eliminate measurement errors caused by voltage splashing distortion.