Reasons for excessive grounding resistance of transformer

Jan 14, 2021

(1) The material of the grounding device is inappropriate. The foundation is not properly filled, the installation process is improper, the ground wire and the ground wire are loosely connected, and the foundation is dry, all of which will greatly increase the ground resistance.

(2) Since the importance of the role of the transformer grounding wire has not been fully understood, the grounding wire may fall off due to the selection of the neutral wire cross-sectional area, damage caused by external force, theft of the ground wire and other reasons. It may cause the ground wire to be disconnected or the ground resistance is too large.


Preventive measures to prevent excessive grounding resistance

Standardize strict construction techniques and burial foundations. The grounding device is usually made of steel pipe, angle steel, flat steel and multi-strand steel. The burial depth should be at least 0.5-0.8m. The construction of grounding equipment usually needs to be carried out simultaneously with the foundation work. Specific requirements are as follows:

① The depth of the grounding groove must meet the design requirements (usually 0.5 to 0.8 m), and the cultivated land must be below the depth of the cultivated land. The width of the ground trench is usually 0.3-0.4 m, and all debris in the trench that affects the contact between ground objects and soil should be removed.

② The specifications of the steel pipe and the depth of penetration into the soil must meet the design requirements, and the grounding contact body must be fixed by penetrating vertically into the ground so that the resistance of the street will not increase. In mountainous areas and areas with high soil resistivity, please avoid the use of tubular grounding devices, and use grounding devices embedded in the ground.

③ The grounding conductor should be placed along the pole and straightened as short as possible to reduce the pulse reactor. The grounding conductor is fixed on the tower by pillars, the linear distance between the pillars is usually 1.0 to 1.5 m, and the turning part is 0.1 m.