+86-312-6775656

Measures to reduce the hazard of corrosive sulfur

Oct 09, 2022

Corrosive Sulfur in Transformer Oil – Causes and Mitigation

With the development of transformers toward larger capacities and higher voltage levels, the issue of corrosive sulfur in transformer oil has drawn increasing attention. Analysis of the causes, occurrence conditions, and influencing factors of transformer faults caused by corrosive sulfur reveals that the behavior of corrosive sulfur in insulating oil is primarily influenced by the transformer's operating conditions. The following measures can be considered to mitigate the harm caused by corrosive sulfur:

(1) Reduce Operating Temperature and Improve Heat Dissipation

Test results indicate that temperature promotes the reaction between corrosive sulfur and copper. As temperature increases, the reaction intensifies. Therefore, during transformer operation, reducing the oil temperature helps slow down sulfur corrosion. Special attention should be given to avoiding local overheating caused by overload operation.

(2) Reduce External Electrical Stress

The electric field promotes the reaction between corrosive sulfur and copper. Corrosive sulfur in oil can corrode copper components during discharge events. Therefore, particular attention should be paid to corrosive sulfur and its destructive effects in high-voltage transformers.

(3) Improve Sealing Performance and Prevent Oxygen Ingress

Oxygen accelerates oil aging and promotes the reaction between corrosive sulfur and copper. To prevent corrosive sulfur-related issues, the transformer must be rigorously vacuum-treated, and the oil conservator must be properly sealed.

Send Inquiry