Frequently used insulating gloves should be tested at least every 6 months, and occasionally used gloves should be tested after each use! In any case, insulating gloves stored in a warehouse should be tested every 12 months. The interval cannot exceed 12 months.
Executive standard
After the user purchases the gloves, if they are found to have been exposed to rain, dampness, mildew, or other abnormal changes during transportation and storage, they should go to a legal testing agency to conduct an electrical performance review test.
An inflation test must be carried out before use, if any damage is found, it cannot be used.
When working, the sleeves of the clothes should be put into the mouth of the tube to prevent accidents.
After use, the internal and external dirt should be scrubbed. After it is dry, sprinkle with talcum powder and place it evenly to prevent damage due to pressure, and do not place it on the ground.
It should be stored in a dry and ventilated warehouse with a temperature range of -15°C to +30°C and a relative humidity of 50% to 80%, away from heat sources, and more than 20 cm away from the ground and walls. Avoid being affected by acid, alkali, oil and other corrosive substances. Do not place it in the open to avoid direct sunlight, and do not place it on the ground.
A preventive test must be carried out after 6 months of use.