+86-312-6775656
Transformer Capacitance Dissipation Tester Tan Delta Test Equipment

Transformer Capacitance Dissipation Tester Tan Delta Test Equipment

Capacitance value of tested article CX is in pF or nF, 1nF=1,000pF.
Dielectric loss value of tested article tgδ is displayed with %.
Send Inquiry
Product Details of Transformer Capacitance Dissipation Tester Tan Delta Test Equipment

Product Introduction

Our winding resistance test equipment, ct pt comprehensive tester, transformer dc resistance tester product line has always been subject to high standards and strict international quality system monitoring. With great enthusiasm, the company is committed to creating and realizing an effective corporate management model. It has developed an advanced computer management system and built a complete information management platform, which has greatly enhanced the core competitiveness of the company. We integrate the corporate value concept into the corporate management system, so that the corporate value concept is transformed into the ideological consciousness and behavioral habits of the majority of workers.

HZ-2000B 10kV/12kV Automatic Tan Delta Test Kit Of Power Transformer

Tan Delta Test Kit price (1)

Tan Delta Test Kit price (2)

Tan Delta Test Kit price (4)

Tan Delta Test Kit price (5)

HZ-2000B_03


Tan Delta Tester

Testable Parameters

Capacitance value of tested article CX is in pF or nF, 1nF=1,000pF.

Dielectric loss value of tested article tgδ is displayed with %.

image002

Performance Features

1. The instrument adopts complex number current method to measure capacitance, dielectric loss and other parameters. The measured result is highly accurate and it is easy to realize automatic measurement.

2. The instrument adopts variable frequency technology to eliminate 50Hz/60Hz power frequency interference. So a reliable data will be reachable even under the strong electromagnetic interference.

3. The instrument adopts large screen LCD . In the process of testing, Chinese menu prompt is visualized and easy to operate.

4. The instrument is easy to operate and the measuring process is controlled by microprocessor. Once a suitable measuring method is selected, the data measurement will complete automatically under the control of microprocessor.

5. The instrument is designed to be an integrated model with reference capacitor and HV power supply in it, enables site test measurement and reduces site wiring.

7. The instrument is equipped with CVT testing function, which can achieve CVT self-exciting testing without external accessories and measure the capacitance and dielectric loss of C1 and C2 by at a time.

8. GST measurement adopts ivddv technology and avoids unstable data provided by previous GST measurement.

9. The instrument provides low voltage shell function of GST. When the bus of 220kV CVT is grounded, dielectric loss measurement can be conducted for C11 without removing 10 kV GST.

10. The instrument has a function of measuring high-voltage dielectric loss. It can carry out dielectric loss test with over 10kV with the help of voltage transformer or series resonance.

12. The instrument has a ground-fault protection function. In case that the instrument is not grounded or grounded incorrectly, the instrument will refuse to enter into normal procedure and output HV. As for the over-current protection function, it will protect the instrument from damage when the tested article is in a short circuit or breakdowns.

13. The instrument has a function of electric shock protection. When the instrument operator suffers an electric shock due to incaution, the instrument will cut off the HV immediately and thus ensure the security of operator.

image004

Tech Data

Accuracy

Cx: ±(reading×1%+1pF)

tgδ

± (reading×1%+0.00040)

Anti-interference

Variable frequency anti-interference, the above accuracy can be reached under 200% interference.

Capacitance range

Internal HV 3pF~60000pF/10kV 60pF~1μF/0.5kV

External HV

3pF~1.5μF/10kV 60pF~30μF/0.5kV

Resolution

Maximum 0.001pF, 4 valid figures.

tgδ range

unlimited, 0.001% resolution, automatic identification for capacitance, inductance and resistance of three tested articles.

Test current range

10μA~1A

Internal HV

Set voltage range: 0.5~10kV

Maximum output current

200mA

Buck-bust method

Continuous stepless regulation

Test frequency

45, 50, 55 single frequency, 45/55Hz automatic dual variable frequency

Frequency accuracy

±0.01Hz

Printer

WH-A7 mini-type thermal printer

Environment temperature

-10℃~50℃

Relative humidity

<90%

Overall dimension

460×360×350mm

Weight

28kg

lQDPKcrtGtmqmW_NAazNAyCw_iF2foFjEn0JNdw6T7ADAg_800_428

image007

image009

Request for quote_

Our company directly face customers, understand customer needs and customer satisfaction with the quality of existing Transformer Capacitance Dissipation Tester Tan Delta Test Equipment, improve product competitiveness. Meanwhile, our products are sold to all over the world. We always take a 'people-oriented leader in science and technology, credit management, a well-known brand' for the purpose, as always, to provide reliable products to customers all over the world.

Hot Tags: HZ-2000B Automatic Transformer Tan Delta Test Kit, China, suppliers, manufacturers, price, for sale, 12 kv tan delta test kit for transformer, tan delta test kit price in india, tan delta test kit manual, tan delta testing of power transformer, Capacitance and Tan delta kit, tan delta testing kit 12 kv HZ-2000B, tan delta test kit specification, tan delta test kit manufacturers in india, Tan Delta Tester of bushing & winding, C-tan delta kit, transformer oil bdv test equipment, transformer dc resistance tester, protection relay test procedure, micro ohm meter, partial discharge free test system, transformer oil tan delta tester

[[ProKeywords]]

SPEC DATA

Send Inquiry

Send a Message