Primary Injection Circuit Test Procedure
Product Introduction
Our Cable And Pipe Locator, transformer dielectric loss tester, battery internal resistance measurement combines the mature technology on the market and our own rich manufacturing experience. Talent first, pursue first-class, lead change, operate in the right way, coexist and win-win. We take the initiative to assume social responsibility while creating economic benefits.
HZ-109S 1000A Primary Current Injection Test Set

Overview
The HZ-109S Primary Current Injection Test Set utilizes ARM chip control technology for output management and a high-capacity toroidal transformer. Equipped with an LCD display meter, it can simultaneously display the primary current, secondary current, turn ratio, and the actuation time of the stopwatch connection (electric potential). Housed in an external aluminum alloy case with a PC panel, the product offers a nice appearance, large output capacity, small size, and light weight. It is primarily suited for CT turn ratio tests, contact resistance tests, and other applications requiring high-current testing in power systems.





The Technology Index
Input Power Supply | AC: 220V· 25A, 50Hz. |
Output Current | AC: 1000A·5V or 500A·10V. |
LCD Screen Digital Display | Simultaneous display of primary current and secondary current as well as the turn ratio; |
The Range of Primary Current | 0~1100A, Resolution: 0.1A; |
The Range of Secondary Current | 0~6A; Resolution: 0.001A. |
Stopwatch | 0.0001~999.99S precision ±5 significant figures. |
Precision | TRUE RMS ±0.5%. |
Duplicate Protection (electronic overload protection and software protection). | |
Usage Environment | Temperature -10~40℃, |
Relative humidity | <80%. |
Volume | 430×260×260mm3. |
Weight | 28kg. |

Safety Precautions
1. In order to ensure the safe operation of test, the instrument should be grounded reliably before the test.
2. The power supply voltage should be set as 220V±10%. Do not input 380V power supply into the instrument, or the instrument will be severely damaged.
3. Connecting or disconnecting the test wire is strictly prohibited when the test is conducting.
4. For the test set, the cable cross-section of input power should be greater than 2mm2, and the cable cross-section of high current output connection should be greater than 70mm2, and the cable length of the output connection should be kept as short as possible.
5. Use paralleling output wherever possible, if only the demand of output current is met.
6. Avoid continuous output in a long time.



We adhere to the business philosophy of 'systematization, scale, standardization, and internationalization' to provide you with strong technical guarantee and comprehensive support for producing high-quality Primary Injection Circuit Test Procedure. 'Starting from customer requirements, ending with customer satisfaction' is the core of our enterprise activities. As long as customers give us a service opportunity, we will return customers satisfaction with practical actions, which is our constant commitment. We are committed to working with customers to find the best applicable solutions.
Hot Tags: HZ-109S 1000A Primary Current Injection Test Set, China, suppliers, manufacturers, price, for sale, high current circuit breaker test set, Primary Current Injection Test Setup, Primary Injection Test Set 1000 amp HZ-109S, programma primary injection test set, primary current injection for relay test set, HZ109S, 1000a generation current, high current injection test 1000a, oil purifying machine, inflatable test transformer, high voltage break down tester, megohmmeter 20kv, ultrasonic partial discharge detector, carbon residue test apparatus