Hmslq High Current Injection 1000A
Product Introduction
The company is committed to providing customers with reliable quality and stable performance Lightning Arrester Tester, relay test unit, high voltage impulse generator products, and to build their own Lightning Arrester Tester, relay test unit, high voltage impulse generator factories for customers. Our company has abundant funds, abundant spot, strong development ability and favorable product price. We rely on the company staff's proficiency in the industry, understanding of the market and sincerity to customers. We are willing to cooperate sincerely with friends and partners from all over the world to create a great business.
HZ-109S 1000A Primary Current Injection Test Set

Overview
The HZ-109S Primary Current Injection Test Set utilizes ARM chip control technology for output management and a high-capacity toroidal transformer. Equipped with an LCD display meter, it can simultaneously display the primary current, secondary current, turn ratio, and the actuation time of the stopwatch connection (electric potential). Housed in an external aluminum alloy case with a PC panel, the product offers a nice appearance, large output capacity, small size, and light weight. It is primarily suited for CT turn ratio tests, contact resistance tests, and other applications requiring high-current testing in power systems.





The Technology Index
Input Power Supply | AC: 220V· 25A, 50Hz. |
Output Current | AC: 1000A·5V or 500A·10V. |
LCD Screen Digital Display | Simultaneous display of primary current and secondary current as well as the turn ratio; |
The Range of Primary Current | 0~1100A, Resolution: 0.1A; |
The Range of Secondary Current | 0~6A; Resolution: 0.001A. |
Stopwatch | 0.0001~999.99S precision ±5 significant figures. |
Precision | TRUE RMS ±0.5%. |
Duplicate Protection (electronic overload protection and software protection). | |
Usage Environment | Temperature -10~40℃, |
Relative humidity | <80%. |
Volume | 430×260×260mm3. |
Weight | 28kg. |

Safety Precautions
1. In order to ensure the safe operation of test, the instrument should be grounded reliably before the test.
2. The power supply voltage should be set as 220V±10%. Do not input 380V power supply into the instrument, or the instrument will be severely damaged.
3. Connecting or disconnecting the test wire is strictly prohibited when the test is conducting.
4. For the test set, the cable cross-section of input power should be greater than 2mm2, and the cable cross-section of high current output connection should be greater than 70mm2, and the cable length of the output connection should be kept as short as possible.
5. Use paralleling output wherever possible, if only the demand of output current is met.
6. Avoid continuous output in a long time.



Our company adopts the world's leading production technology and strict quality management and high-precision testing equipment, so as to ensure the continuity and stability of the quality of all Hmslq High Current Injection 1000A. Our company has a skillful sales team, strong economic foundation, great technical force, advanced equipment, complete testing means, and excellent after-sales services. We sincerely welcome all guests to setup small business associations with us on the basis of mutual positive aspects.
Hot Tags: HZ-109S 1000A Primary Current Injection Test Set, China, suppliers, manufacturers, price, for sale, high current circuit breaker test set, Primary Current Injection Test Setup, Primary Injection Test Set 1000 amp HZ-109S, programma primary injection test set, primary current injection for relay test set, HZ109S, 1000a generation current, high current injection test 1000a, oil density tester, Karl Fischer Moisture Analyzer, cloud and pour point apparatus, transformer demagnetization test equipment, transformer oil dielectric loss tester, Single Phase Relay Test Set