HZSF1412 SF6 Gas Recycling Device SF6 Gas Recovery Machine General Description This recovery device adopts an oil compressor imported from Italy, which is used for the recovery device of SF6 gas, recovering SF6, the displacement of the compressor can reach 6.5m3/h, and the maximum output...
Send Inquiry
Product Details ofHZSF1412 SF6 Gas Recycling Device SF6 Gas Recovery Machine

Huazheng Electric Manufacturing (Baoding) Co., Ltd. is one of the leading manufacturers and suppliers of hzsf1412 sf6 gas recycling device sf6 gas recovery machine in China. Please feel free to buy high quality equipment for sale here from our factory. Good service and reasonable price are available.

 

HZSF1412 SF6 Gas Recycling Device SF6 Gas Recovery Machine

 

General Description

This recovery device adopts an oil compressor imported from Italy, which is used for the recovery device of SF6 gas, recovering SF6, the displacement of the compressor can reach 6.5m3/h, and the maximum output pressure is 4.5MPa (the pressure of the device is controlled at 3.8MPa). The compressor is a high-pressure compressor with low power consumption, which greatly reduces the volume and weight of the SF6 recovery device.

 

Equipment Parameters

Compressor displacement: 6.5m3/h

Maximum exhaust pressure: 4.5MPa (already set to 3.8MPa)

Maximum inlet pressure: 0.5MPa

SF6 recovery amount: about 1kg/2 minutes (related to the inlet pressure)

Recovery final pressure: 0MPa (relative pressure)

Power supply: 380V 50Hz 3Kw

Weight: about 60kg

1. Standard configuration:

( 1 ) The outlet and inlet are M27*1.5 flat connectors.

( 2 ) Pointer type outlet and inlet pressure indication

( 3 ) 380V 10A power cord.

 

Operating Instructions

1. Power Connection
Insert the standard power cord into a power socket that meets the specified requirements and turn on the power switch. The compressor cooling fan will start running.

Note: This operation must be performed continuously. At all times-even after work is completed-the main power supply should be kept connected for at least 1 minute to ensure adequate heat dissipation.

2. Compressor Suction Pressure Adjustment
With external piping connections correctly configured, first adjust the suction pressure reducing valve of the compressor to ensure that the pressure at the suction port is lower than 0.5 MPa. Under this condition, the compressor can start normally and enter the working state.

3. Start/Stop Control
Press the green start button to start the recovery device. Press the red stop button to stop the recovery device.

4. Overpressure Protection
If the outlet pressure becomes too high (up to 3.8 MPa) before shutdown, the internal protection system will automatically stop the compressor.