+86-312-6775656

XZTZ3080 Three-channel Transformer DC Resistance Tester

Sep 19, 2024

XZTZ3080 three -channel DC resistance tester, also known as power frequency grounding resistance tester, grounding resistance meter, etc., is a commonly used instrument for testing commonly used instruments for measuring grounding resistance. It adopts new frequency conversion AC power supply, dual-frequency measurement technology, large touchable color screen and microprocessor technology to meet the requirements of two-wire, three-wire and four-wire test impedance, and can measure soil resistivity, step voltage, distributed potential, touch voltage , current phase angle and other parameters. It is suitable for telecommunications, electric power, meteorology, computer room, oil field, power distribution lines, tower transmission lines, gas stations, factory grounding grids, lightning rods, etc. It meets the standards of power substations and lightning protection devices. The instrument test is accurate, fast, simple, stable and reliable.

The tester outputs an open-circuit rated voltage of 27 V and a maximum short-circuit current of 20 A. Microprocessor control and automatic dual-frequency technology can accurately measure and calculate the grounding impedance value under the 50Hz power frequency state under the strong interference state, and the large-screen display is clear at a glance. At the same time, 500 groups of data are stored, and the resistance measurement range is 0.1 uΩ ~ 5000Ω . The measurement data can be printed by thermal printer , U disk and PC software can be exported .

The three-channel DC resistance tester consists of a host, test lines, etc., and has functions such as reading, viewing, saving, and printing historical data.

XZTZ3080

Range and Accuracy

measure current

Measuring range

precision

Resolution

20A

0.0001~1.0000mΩ

±0.2%FS±10dgt

0.1uΩ

1.001~10.000mΩ

±0.2%FS±10dgt

0.0 01mΩ

10.01~100.00mΩ

±0.2%FS±10dgt

0.01mΩ

100.1~1000.0mΩ

±0.2%FS±10dgt

0.1mΩ

10A

0.0001~1.0000mΩ

±0.2%FS±10dgt

0.1uΩ

1.001~10.000mΩ

±0.2%FS±10dgt

0.0 01mΩ

10.01~100.00mΩ

±0.2%FS±10dgt

0.01mΩ

100.1~1000.0mΩ

±0.2%FS±10dgt

0.1mΩ

5A

0.001~10.000mΩ

±0.2%FS±10dgt

0.001mΩ

10.01~100.00mΩ

±0.2%FS±10dgt

0.01mΩ

100.1~1000.0mΩ

±0.2%FS±10dgt

0.1mΩ

1.001~5.000Ω

±0.2%FS±10dgt

0.001Ω

2A

0.001~10.000mΩ

±0.2%FS±10dgt

0.001mΩ

10.01~100.00mΩ

±0.2%FS±10dgt

0.01mΩ

100.1~1000.0mΩ

±0.2%FS±10dgt

0.1mΩ

1.001~10.000Ω

±0.2%FS±10dgt

0.001Ω

0.5A

0.01~100.00mΩ

±0.2%FS±10dgt

0.01mΩ

100.1~1000.0mΩ

±0.2%FS±10dgt

0.1mΩ

1.001~10.000Ω

±0.2%FS±10dgt

0.0 01Ω

10.01~50.00Ω

±0.2%FS±10dgt

0.01Ω

0.2A

10.01~100.00Ω

±0.2%FS±10dgt

0.01Ω

100.1~1000.0Ω

±0.2 5 %FS±15dgt

0.1Ω

1001~5000Ω

±0. 3 %FS± 20dgt

1Oh

Temperature characteristics : plus test accuracy × 0.1/ °C within the operating temperature range . ( outside 18 ℃ to 28 ℃ )

at 8 °C : ±0.2%FS±10dgt (basic accuracy) + 0.1 × 10 (temperature difference ) × (0.2 %FS + 10dgt )= ± 0.4 %FS ± 2 0dgt

 

Technical indicators

Function

It is mainly used to measure the DC resistance of transformers, transformer winding resistance, grounding network connection continuity, wire resistance of cables, contact resistance of switches, connectors, relays, coils, motors, transformer winding resistances and metal riveting resistance, metal components Connection resistance test, low value resistance test, contact resistance test, etc.

Resistance range

0.1uΩ - 5000Ω _

power supply

AC 220V 10A (50Hz)

Rated measuring power

12 00W

Backlight

Adjustable backlight brightness

measurement method

Four-wire test

Short circuit current output

0.2 A, 0.5 A, 2 A, 5 A, 10 A , 20A ( 6 settings)

Short circuit maximum current

DC 20A ±10%

No-load maximum voltage

DC 27V ± 15 % _

display screen

7 -inch touch color screen

Overload protection

Have

automatic discharge

Have

U disk interface

Copy and save data

USB interface

With a USB interface , it can be connected to the host computer to view data

Measurement instructions

Measurement progress display, real-time measurement display

Meter size

Length, width and height: 400mm × 300mm ×210mm

Standard test lead length

4 strips (red 5m, blue 5m, yellow 5m , green 5m 2 each )

Print

Built-in thermal printer

Paper Specifications

57*40mm

data storage

500 sets of measurement data storage

Data access

Have

overflow display

Over range overflow function: "OL" symbol display

Power consumption

Standby: ≤ 110W / Measurement: ≤ 15 00W

quality

Gauge: 7 kg

Working temperature and humidity

-10℃~40℃; below 80%rh

Storage temperature and humidity

-20℃~60℃; below 70%rh

Insulation resistance

10MΩ or more (500V between circuit and case)

Pressure resistance

AC 3700V/rms (between circuit and case)

Electromagnetic properties

IEC61010-4-3, radio frequency electromagnetic field≤1V/m

Suitable for safety regulations

IEC61010-1, IEC1010-2-31, IEC61557-1, 5, IEC60529 (IP54), pollution, etc. 2, CAT Ⅲ 300V

Send Inquiry