+86-312-6775656

XZTCT-100 Current Transformer CT PT Test Set

Jan 07, 2025

XZTCT-100 Current Transformer CT PT Test Set

 

Characteristics

★ Full-featured, not only satisfy the test requirements of various CTs (include TP class), such as the excitation characteristics (i.e., volt-ampere characteristics), ratio, polarity, secondary winding resistance, secondary burden, ratio error and phase displacement, but can also be used for the tests of various PTs, including excitation characteristics of the electromagnetic unit, ratio, polarity, secondary winding resistance, ratio error and phase displacement.

★ Automatically give CT, VT parameters, including knee point voltage / current, 10% error curve, the accuracy limit factor (ALF), instrument security factor (FS), the second time constant (Ts), remanence coefficient (Kr), saturated and unsaturated inductance etc.

★Test meet IEC60044 GB1208 (-1) GB16847 (IEC60044-6) became etc all kinds of transformer standards, and in accordance with the transformer types and levels of automatic choose which standard test

★ Based on advanced principle of low-frequency test method that can meet the CT test on knee voltage up to 30KV.

★Friendly interface beautiful, all Chinese graphic interface

★ The instrument can store 2000 groups of test data that won't be lost when power off. After test ended, the data can be coped to PC by USB disk for analysis and being transformed into WORD report.

★ Test is simple and convenient, one-click can complete tests of CT secondary resistance, excitation, ratio and olarity.

★ Easy to carry, because the weight is less than 9Kg.

1.2 Panel

The instrument panel structure is as shown in right figure.

·• Red S1, black S2 terminal: test power output

·• Yellow S1, black S2 terminal: measure output voltage

• Green P1, black P2 terminal: measure inductive voltage

• Keyboard: Enter the value and operational command

news-290-260

• LCD screen: GUI

1.3 Technical Parameter

 

 

Usage

Class P/TP CT & VT

Output

0~180Vrms,12Arms,18A(peak value)

CT Ratio

Range

1~30000

accuracy

±0.2%

PT Ratio

Range

1~30000

accuracy

±0.2%

Phase

Range

±5min

accuracy

0.5min

DC resistance

Range

0~300Ω

accuracy

2%±2mΩ

Burden

Range

0~300VA

accuracy

2%±0.2VA

Power supply

AC220V±10%,50Hz

Environmental Conditions

Operating temperature :-10οC ~50οC,Humidity :≤90%

Weight and Dimensions

Dimensions:340 mm×300 mm×150mm,Weight<9kg

Send Inquiry