How To Operate SF6 Comprehensive Tester?

Jan 11, 2021

1. Connect SF6 equipment

Connect the threaded end of the measuring pipe to the switch connector, tighten it with a wrench, and close the needle valve at the other end of the measuring pipe; then insert one end of the quick connector on the test pipe into the sampling port on the tester; connect the exhaust pipe to Air outlet: Finally, connect the switch connector to the SF6 electrical equipment measurement interface, and tighten it with a wrench.

2. Warm-up and self-check

Turn on the power switch of the instrument, and the instrument enters the warm-up and self-check process.

3. Check the battery

It is recommended to use AC power first. When using DC power, please check the battery power displayed in the upper right corner. If the power is less than about 30%, please turn off the battery and continue using it after charging.

4. Start measuring

After the instrument finishes preheating and self-checking, it automatically enters the "main menu". Press the "data measurement" button to enter the measurement interface and automatically measure. At this time, turn on the flow valve and the gas chamber protection knob on the front panel of the tester, and then adjust the measurement pipeline The needle valve on the upper side adjusts the flow to 0.2LPM.

5. Store data

After the equipment measurement is completed, you can save the data in the instrument, press the "Save" key to call up the operation menu, the specific operation method is shown in the next section.

6. After the measurement, close the needle valve on the measuring pipe and the regulating valve on the tester.

Remove the adapter from the SF6 electrical equipment. If you need to continue measuring other equipment, do not turn off the power of the instrument, and follow the steps above to perform the next measurement.

7. After the measurement, turn off the power of the tester.

Operate the SF6 comprehensive tester in the above order to ensure the smooth progress of the entire measurement process.