160KV 250KV 350KV 2mA/3mA/5mA DC Hipot Test Set DC High Voltage Generator

Jun 19, 2022

DC high-voltage generators are mainly used for DC withstand voltage tests on high-voltage electrical equipment such as zinc oxide arresters, power cables, transformers, circuit breakers, generators, etc. or DC leakage current test.

Voltage kV
Current
mA
Control box
DC high voltage generator

Rated voltage
External dimension(mm)
Weight
(kg)
External dimension(mm)
Weight
(kg)
60/2-10
60kV
310*250*230
5
470*260*220
6
80/2-10
80kV
310*250*230
6
490*260*220
8
100/2-10
100kV
310*250*230
6
550*260*220
8
120/2-10
120kV
310*250*230
7
600*260*220
10
200/2-5
200kV
310*250*230
8
1000*280*270
20
250/2-5
250kV
310*250*230
8
1130*290*270
20
300/2-5
300kV
310*250*230
9
1300*290*270
22
350/2-5
350kV
310*250*230
9
1370*290*270
24
Output polarity
Negative voltage polarity, zero voltage start, linear continuous adjustable
Working power supply
50HZ AC220V±10%
Voltage measurement accuracy
± 0.5% ± 2 words, minimum resolution 0.1kv, measurement range (range 10% to 1.1 times of range)
Current measurement accuracy
± 0.5% ± 2 words, minimum resolution: 0.1 μ a for anti-impact ammeter, 1 μ a for control box,
measuring range
(10% of range to full scale).
Ripple coefficient
≤0.5%
Voltage stability
Random fluctuation, ≤ 0.5% when the grid voltage changes ± 10%
Operation mode
Intermittent working system, less than 30 minutes under rated load
Working conditions
Temperature: 0-40 ℃, humidity less than 90%
Storage conditions
Temperature: -10℃~40℃, humidity less than 90%
Altitude
Below 3000 meters

The Use Of Discharge Rod

1. The special discharge rod should not be in direct contact with high-voltage DC discharge, and should be kept at a distance. When the tip of the discharge rod initially produces corona discharge, and the voltage on the test object gradually drops by 20% of the test voltage, then touch the discharge rod to the shell of the microammeter. discharge. Finally, hang the ground wire of the grounding end of the discharge rod directly on the test object.

2. Special attention is not allowed to directly discharge the ground wire on the shell of the high-voltage microammeter, so as to avoid the damage of the high-voltage microammeter caused by the strong impulse discharge current.