Huazheng HZJY-20K-Z High Voltage Insulation Tester 20kV Megohmmeter Parameter ● AC power supply: 120V ± 10%, 50 / 60 Hz, 20 VA ● output voltage accuracy: 100% to 110% of nominal value ● output voltage monitoring accuracy: ± 5% ± 10V ● voltage measurement range: AC: 30-600v (50Hz / 60Hz), DC:...
Product Details ofHigh Voltage Insulation Tester 20kV Megohmmeter

 

High Voltage Insulation Tester 20kV Megohmmeter

 

The HZJY-20K-Z HV insulation tester is a specialized instrument designed to measure the insulation resistance of electrical equipment. It is suitable for insulation testing and maintenance of transformers, current transformers, generators, high-voltage motors, and similar devices. 

 

Parameter

range accuracy

500V

1000V

2500V

5000V

10000V

15000V

20000V

Not specified

<100K

<100K

<100K

<100K

<100K

<100K

<100K

±5%rdg

100K-10G

100K -20G

100K -50G

100K -100G

100K-200G

100K-300G

100K-400G

±20%rdg

10G-100G

20G-200G

50G-500G

100G-1T

200G-2T

300G-3T

400G-4T

Not specified

>100G

>200G

>500G

>1T

>2T

>3T

>4T

 

Instrument Using

measured DAR:

Select more than 1 minute length measurement.

Select the appropriate voltage and start.

The instrument automatically records the resistance values at 15 seconds and 60 seconds, and calculates the absorption ratio after 60 seconds.

Absorption ratio calculation method: DAR = R60 / R15;

measured PI :

Select more than 10 minute length measurement.

Select the appropriate voltage and start.

The instrument automatically record 15S, 60S and 600S resistance, and calculate the polarization index after 600 seconds.

Polarization index calculation method : PI= R600/R60;

DD

This test is applicable to the diagnosis of multi-layer insulation. It is a good method to judge the bad situation in multi-layer insulating objects by measuring the discharge current value and the capacitance value of the tested object 1 minute after the test is completed.

DD value = current value 1 minute after test (mA) / voltage value at test completion (V) / capacitance value (F)

DD value

2.0 less

2.0 ~ 4.0

4.0 ~ 7.0

7.0 above

criteria

Best

Good

Warning

Bad

This judgment standard is the target value, which may need to be adjusted or changed by the user according to experience. It is a test method developed to test the high-voltage generator of power stations in Europe.

 

Packing List

No.

Item

Qty

1

Host

1

2

High voltage shielding test line

1

3

Red silicone test line

1

4

Green silicone test line

1

5

Black Silicone test line

1

6

Power Line

1

7

USB drive

1

8

USB cable

1

 

lQDPKcrtGtmqmW_NAazNAyCw_iF2foFjEn0JNdw6T7ADAg_800_428

image014

image016

Request for quote_

Hot Tags: high voltage insulation tester 20kv megohmmeter, China, suppliers, manufacturers, price, for sale, 20kv high voltage insulation tester, 30 kv insulation resistance tester, 30kv insulation tester, DC High Voltage Insulation Tester, Insulation Resistance Tester 10kv, Lightning Arrester Tester

Send Inquiry

(0/10)

clearall