What are the causes of partial discharge?

Apr 16, 2024

Partial discharge can occur inside bubbles, oil films, or at the edges of conductors (electrodes) in insulation structures, and become forms of internal discharge (gas or oil), surface discharge, corona discharge, etc. Therefore, corona discharge is narrower than partial discharge, but does not form channels between electrodes. Partial discharge is often difficult to avoid for high-voltage electrical products.
This is because insulation materials or structures often contain air gaps or oil films that are more prone to breakdown than solid insulation media during the manufacturing process. For example, casting transformers and transformers, plastic cables, and adhesive paper sleeves inevitably contain bubbles during the manufacturing process. In the oil immersed insulation of high-voltage electrical appliances, there is an oil film between the paper layers.
The dielectric constant of air and mineral oil is lower than that of solid media, so under the action of an electric field, they often bear higher field strengths than solid media. However, the breakdown strength of air and oil is lower than that of solid media. Therefore, when the applied voltage rises to a certain value, it will cause local breakdown of air or oil, resulting in insulation partial discharge.
In addition, due to the concentrated electric field at the edge of the electrode, the electric field strength at the edge is particularly high. For example, the edge of the sleeve electrode and the outlet of the high-voltage motor coil are prone to discharge. Local discharge often occurs in the adhesive tape sleeve and the winding of the high-voltage motor under working voltage.
In the design and manufacturing of high-voltage cables and capacitors, the working field strength is generally lower than the initial discharge field strength of oil paper insulation. However, under the action of an electric field, insulation paper ages due to the impact of high-energy charged particles. At the beginning, the gas can be absorbed, but over time it will form bubbles and cause partial discharge.
Partial discharge is mainly generated under AC sinusoidal voltage, which directly endangers the normal operation of insulation. Other types such as lightning overvoltage and operating overvoltage, due to their short duration and low probability of occurrence, are not sufficient to cause significant discharge hazards. Under DC voltage, the repetition rate of discharge is much lower than that of AC voltage, so it is not taken seriously by people.
When the DC voltage is applied, the discharge repetition rate of impregnated paper cables should reach the discharge repetition rate that occurs at AC voltage. The discharge voltage is about 6-11 times that of AC voltage. The reason is that the discharge repetition rate under AC voltage is much higher than that under DC voltage, so its harm is serious.
The corona discharge at the tip or electrode edge is mostly exposed to air, and the damage to the medium depends on whether the corona comes into contact with the material. If it does not come into direct contact with the material, it is indirectly caused by the generated ozone or other corrosive products.