Technical data
Measuring principle: Dual wavelength non-dispersive infrared spectrometer (NDIR)
Sensitivity: 1 ppmv 3.43g/year, 1.81×10-5 atm cc/sec (or mbar L/s) other gases and moisture will not affect the sensitivity
Humidity: Unaffected in the range of 0-100%rh, it should be used without condensation and pollution.
Response time: about 1 second Repeatability: <0.3%
Operation: Lithium battery, working time is more than 8 hours 100-265V AC 50/60Hz
Alarm: Sound and display alarm through 3 LEDs
Measurement results: Measured in ppmv range: 0 ~ 2,000 ppmv Two displays (manually operated device and instrument panel)
Accuracy: 0-100 ppm v ± 5 % of measurement 100-2,000 ppm v ± 2 % of measurement
Calibration/Maintenance: Every 5 years
Temperature: Storage: -10℃ to 60℃ / Operation: 0℃ to 45℃
What is the difference between the HZIR-1000 SF6 infrared quantitative detector and the German (German GAS) model, and what are the similarities and differences?
1. The HZIR-1000 type is a touch color screen, and the imported one is an LCD screen.
2. The HZIR-1000 is handheld, and the imported one is an extra back host.
3. HZIR-1000 has save function
The imported HZIR-1000 can achieve and surpass the above 3 points. The HZIR-1000 sensor and (German GAS) use a sensor from the same company.