The power frequency test transformer itself should have good insulation, but the insulation margin is small, and overvoltage should be strictly limited during the test process. The capacity of the test transformer is generally not large, and the continuous operation time is not long, and the heating is relatively light, so there is no need for a complex cooling system. Large leakage reactance and low short-circuit current can reduce the requirements for mechanical strength and save manufacturing costs.
The principle of the test transformer is the same as that of a general power transformer, but it has many structural characteristics
1. High voltage and small capacity. Due to the high voltage, the high-voltage winding needs to use thicker insulation and wider oil gap distance,
Therefore, the leakage magnetic flux of the test transformer is relatively high, and the short-circuit reactance value is also relatively high.
2. It will not be affected by atmospheric overvoltage and operating overvoltage, so insulation can adopt a smaller safety factor.
3. Usually, the continuous working time of the test transformer is short, it will not overheat, and there is no need to use a complex cooling system. It is precisely because the test transformer allows for a low temperature rise that it can only operate for a short time at rated voltage and rated power.
4. The short-circuit current of the test transformer is small, and it is not necessary to consider the short-circuit mechanical strength of the winding.
5. Due to the influence of voltage waveform on the test results, the waveform distortion of the test transformer should be minimized as much as possible. Therefore, high-quality iron cores and lower magnetic flux density should be used.
6. In order to reduce interference with partial discharge tests, the partial discharge voltage itself should be sufficiently high. Therefore, a reasonable insulation structure and sound insulation treatment process should be adopted.