1. Lightning arresters for 10kV and below and cables with a length of 5km for dc hipot tester at 60kV/5mA;
2. 120kV/5mA dc hipot tester for lightning arresters of 35kV and below and cables of 3km length;
3. 120kV/10mA dc hipot tester for lightning arresters of 35kV and below and cables of 5km length
Addendum: If only testing 10 kV zinc oxide lightning arresters, a 60 kV 2mA dc hipot tester device can be selected
If testing cables, 60 kV 5mA is required
The smaller the leakage current during the testing of zinc oxide lightning arresters, the better. The machine mainly tests lightning arresters. Can read leakage current. If using this instrument to conduct DC high voltage tests on cables, it is necessary to choose a 10mA one, which will result in higher power consumption and greater safety.
Selection of lightning arresters and cable DC withstand voltage tests for different voltage levels
Dec 12, 2024