The selection of DC high-voltage generator should refer to the following principles:
(1) Output voltage.
It shall be determined according to the highest test voltage of various tested objects, with margin reserved.
(2) Output current.
Determine according to the maximum test current of various tested objects, and consider more than 30% margin, usually 2-10mA.
(3) Ripple factor.
DC high-voltage generator with ripple factor less than or equal to 1.0% shall be selected for leakage current, conductance current and DC 1mA voltage test of various lightning arresters; When conducting DC leakage current and DC withstand voltage tests on general high-voltage electrical equipment, it is allowed to select DC high-voltage generator with ripple factor not greater than 3.0%; In comprehensive consideration, DC high-voltage generator with ripple factor less than or equal to 1.0% should be selected.
(4) Output voltage measurement error.
If the test duration does not exceed 60s, the test voltage measurement error shall be kept within ± 1%. If the test duration exceeds 60s, the test voltage measurement error can be kept within ± 3%. Generally, DC voltage measurement error within ± 1% shall be selected.
(5) Output voltage polarity.
In the field DC voltage test, in order to prevent flashover of external insulation and easily find defects such as insulation moisture, negative DC voltage is usually used.
(6) Measurement function and accuracy.
The DC high-voltage generator shall have the output voltage measurement function, and the measurement error of the voltage divider shall not exceed ± 1.0%; The voltage equalizing cover of the DC high-voltage generator is equipped with a digital microammeter to directly measure the leakage current at the high-voltage side or an external microammeter can be connected at the high-voltage side. The measurement error of the microammeter should not exceed ± 1.0%; DC high-voltage generator is provided with × 0.75 function, which is very convenient for measuring the leakage current of gapless metal oxide arrester under 0.75 times U1mA voltage.
(7) Height.
When the output voltage, current, ripple coefficient, measurement accuracy and other technical indicators of the DC high-voltage generator are the same, the one with light weight and small volume is better. However, attention should also be paid to the size. The height of the insulation barrel of 200KV DC high-voltage generator produced by some manufacturers is less than 0.5m, which is acceptable under laboratory conditions or dry environments. However, in the field, especially when the relative air humidity is high, the surface creepage of the insulation barrel is serious, which will directly affect the technical performance of the DC high-voltage generator, and even cause surface flashover. For DC high-voltage generator with rated voltage of 200KV, the effective height of insulation barrel should not be less than 0.6m.